Summary for Test 2025-06-22-1-2

Test performed: ASTM C39-18

Project Information

Project IdentifiersProject ID: 994358
DEA: 033J3304
EFIS: 0322000251
DIST-CO-RTE-PM03-SAC-12-0/0.5
Award DateNot set
Closeout DateNot set
Work DescriptionMMBN Project. Replace backup drive system, replace lift span deck, install hydraulic barrier system and new generator, replace electrical control system, install new traffic gates and elevators, traffic control,
Location DescriptionNot set
QA Service Level1 (Verified on 10/25/2022)

Sample Information

Sample Taken Date06/22/2025 Sample Unique Key1
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing06/22/2025
Sample typeQuality Assurance A brief description of the sample15 - 4x8 and 2 - 6x12 concrete cylinders
The quantity of what the sample constitutes19 CY From where was the sample collectedJob Site
First name of sampler or witnessed byMichael Last name of sampler or witnessed byMullins
Title of samplerFFS Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility namePrecision Concrete Materials Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameRio Vista Bridge Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number90479AFP LWA-LWF-A2
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedTBD
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedconcrete sample from wheelbarrow Where the material sample would have been placed if not sampledbridge deck pour 6A
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2025-06-22-1
DIME Test ID: 2025-06-22-1-2
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2025-06-30

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Stephen Haynes
Date of test: 06/30/2025
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 72780 lb
Maximum load on cylinder 2: 74352 lb
Maximum load on cylinder 3: 68004 lb
Type of fracture pattern of cylinder 1: 5
Type of fracture pattern of cylinder 2: 5
Type of fracture pattern of cylinder 3: 5
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 8 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 5790.0 psi
Compressive strength of cylinder 2: 5915.0 psi
Compressive strength of cylinder 3: 5410.0 psi
Compressive strength (to nearest 10 psi): 5710 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 6/30/2025