Summary for Test 2025-05-05-6-1

Test performed: ASTM E23-18

Project Information

Project IdentifiersProject ID: 994358
DEA: 033J3304
EFIS: 0322000251
DIST-CO-RTE-PM03-SAC-12-0/0.5
Award DateNot set
Closeout DateNot set
Work DescriptionMMBN Project. Replace backup drive system, replace lift span deck, install hydraulic barrier system and new generator, replace electrical control system, install new traffic gates and elevators, traffic control,
Location DescriptionNot set
QA Service Level1 (Verified on 10/25/2022)

Sample Information

Sample Taken Date05/05/2025 Sample Unique Key6
Will the laboratory/organization for which you are a member perform testing on this material sample?No Date that the sample was received by the laboratory/organization performing the testing05/05/2025
Sample typeAcceptance A brief description of the sampleA709 Steel Check Sample
The quantity of what the sample constitutes1/2 inch plate From where was the sample collectedFabricator
First name of sampler or witnessed byStephen Last name of sampler or witnessed byHaynes
Title of samplerQuality Assurance Inspector Telephone number of sampler5105931179
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameXKT Engineering Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameRio Vista Bridge Bid ItemNot set

Material Information

Material TypeSMTL TM6 - Steel Check Sample Plate Heat Number(s)22A6726-01
Material SpecificationA709 Grade50WT3
Thickness.5 ShapeSquare
Metal Foundry Manufacturer (Mill)Nucor Steel Tuscaloosa Plate Dimension60" x 72"

Test Details

DIME Sample ID: 2025-05-05-6
DIME Test ID: 2025-05-05-6-1
Testing Lab: Atlas - Oakland
Test Method: ASTM E23-18: Standard Test Methods for Notched Bar Impact Testing of Metallic Materials (Charpy Impact)
Test Release Date: 2025-07-08

Test Results


Input Type: Calculated
Tester's full name: Andrew Auvinen
Date of test: 07/08/2025
Temperature Required: 40 oF
Minimum Energy Required: 25 ftlb
Test Temperature 1: 40 oF
Impact Energy 1: 258 ftlb
Impact Energy 2: 258 ftlb
Impact Energy 3: 257 ftlb
Striker Radius: 10 mm
Average Impact Energy: 258 ftlb
Value Exceeds The Machine Capacity?: No
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 7/8/2025