Summary for Test 2025-04-02-1-2
Test performed: ASTM C39-21Project Information
| Project Identifiers | Project ID: 1001009 DEA: 043X0504 EFIS: 0425000193 |
|---|---|
| DIST-CO-RTE-PM | 04-SON-116-10.4 |
| Award Date | Not set |
| Closeout Date | Not set |
| Work Description | Apply traffic control systems, remove dirt and debris from slide, install RSP, drainage, erosion control, and reestablish MGS System. |
| Location Description | In Sonoma County on State Route 116 at PM 10.4 near Montesano. |
| QA Service Level | 1 (Verified on 03/10/2025) |
Sample Information
| Sample Taken Date | 04/02/2025 | Sample Unique Key | 1 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 04/03/2025 |
| Sample type | Quality Assurance | A brief description of the sample | Type II Cement |
| The quantity of what the sample constitutes | 18 CY | From where was the sample collected | Job Site |
| First name of sampler or witnessed by | Kyle | Last name of sampler or witnessed by | Whitman |
| Title of sampler | ASR | Telephone number of sampler | |
| Laboratory sample identification | Linked DIME Sample ID | ||
| The fabricator/manufacturer/facility name | River Ready Mix | Transportation Laboratory (TL) Number | |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
| Structure name | Bid Item | Not set |
Material Information
| Material Type | Concrete | The concrete mix design number | 72203043F |
|---|---|---|---|
| The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 001 | |
| Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
| A detailed description of where the material sample was collected | Concrete from wheelbarrow | Where the material sample would have been placed if not sampled | |
| From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2025-04-02-1
DIME Test ID: 2025-04-02-1-2
Testing Lab: Quality Assurance Engineering, Inc dba Consolidated Engineering Laboratories
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2025-05-02
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: MGomez
Date of test: 04/30/2025
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Apparent mass of submerged cylinder 1: 9 lb
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 95090 lb
Maximum load on cylinder 2: 95750 lb
Maximum load on cylinder 3: 94770 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 29 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 7560.0 psi
Compressive strength of cylinder 2: 7620.0 psi
Compressive strength of cylinder 3: 7540 psi
Compressive strength (to nearest 10 psi): 7570 psi
Serial number of delivery ticket, if available: no data
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 5/2/2025 ✔