Summary for Test 2025-03-30-1-4

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 994358
DEA: 033J3304
EFIS: 0322000251
DIST-CO-RTE-PM03-SAC-12-0/0.5
Award DateNot set
Closeout DateNot set
Work DescriptionMMBN Project. Replace backup drive system, replace lift span deck, install hydraulic barrier system and new generator, replace electrical control system, install new traffic gates and elevators, traffic control,
Location DescriptionNot set
QA Service Level1 (Verified on 10/25/2022)

Sample Information

Sample Taken Date03/30/2025 Sample Unique Key1
Date that the sample was received by the laboratory/organization performing the testing03/30/2025 Sample typeQuality Assurance
A brief description of the sample15 - 4x8 and 9 - 6x12 concrete cylinders The quantity of what the sample constitutes19 CY
From where was the sample collectedJob Site First name of sampler or witnessed bySteve
Last name of sampler or witnessed byHaynes Title of samplerQuality Assurance Inspector
Telephone number of sampler5105931179 Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility namePrecision Concrete Materials
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure nameRio Vista Bridge
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number90479AFP LWA-LWF-A2
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected17839
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedconcrete sample from wheelbarrow Where the material sample would have been placed if not sampledbridge deck pour 1A
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2025-03-30-1
DIME Test ID: 2025-03-30-1-4
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2025-04-27

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Yannick Aranas
Date of test: 04/27/2025
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.01 in
Average diameter of cylinder 2: 4.01 in
Average diameter of cylinder 3: 4.02 in
Maximum load on cylinder 1: 71790 lb
Maximum load on cylinder 2: 70135 lb
Maximum load on cylinder 3: 64865 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 5
Type of fracture pattern of cylinder 3: 5
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.63 in^2
Cross sectional area of cylinder 2: 12.63 in^2
Cross sectional area of cylinder 3: 12.69 in^2
Compressive strength of cylinder 1: 5684.1 psi
Compressive strength of cylinder 2: 5553.0 psi
Compressive strength of cylinder 3: 5111.5 psi
Compressive strength (to nearest 10 psi): 5450 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 4/27/2025 ✔