Summary for Test 2024-10-28-26-2

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 994376
DEA: 044J4604
EFIS: 0415000351
DIST-CO-RTE-PM04-SON-116-11.8/R12.2
Award Date04/16/2024
Closeout DateNot set
Work DescriptionREPLACE CURB RAMPS, SIDEWALK, DRIVEWAY, LIGHTING, & SIGNAL.
Location DescriptionSONOMA COUNTY AT GUERNEVILLE FROM BROOKSIDE LANE TO OLD RIVER ROAD
QA Service Level1 (Verified on 10/27/2022)

Sample Information

Sample Taken Date10/28/2024 Sample Unique Key26
Will the laboratory/organization for which you are a member perform testing on this material sample?No Date that the sample was received by the laboratory/organization performing the testing10/29/2024
Sample typeQuality Assurance A brief description of the sampleConcrete for Barriers
The quantity of what the sample constitutes31 CY From where was the sample collectedJob Site
First name of sampler or witnessed byVenkat Varun Last name of sampler or witnessed byGalla
Title of samplerASR Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameShamrock Materials Inc Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberD20115E1
The truck number from where the sample was collected2 The batch plant ticket number from where the sample was collected713489
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedConcrete collected from the back of truck. Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2024-10-28-26
DIME Test ID: 2024-10-28-26-2
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2024-11-25

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Nikhil Moon
Date of test: 11/25/2024
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 77368 lb
Maximum load on cylinder 2: 76488 lb
Maximum load on cylinder 3: 78060 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 0.99
Correction factor for cylinder 2: 0.99
Correction factor for cylinder 3: 0.99
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 6093.4 psi
Compressive strength of cylinder 2: 6024.1 psi
Compressive strength of cylinder 3: 6147.9 psi
Compressive strength (to nearest 10 psi): 6090 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 11/25/2024