Summary for Test 2024-10-18-42-1

Test performed: CTM 670-December 2013

Project Information

Project IdentifiersProject ID: 1000297
DEA: 010P0704
EFIS: 0124000162
DIST-CO-RTE-PM01-MEN-1-82.1/92.9
Award Date03/18/2024
Closeout DateNot set
Work DescriptionMajor items of work include traffic control, reconstruct and stabilize roadway, install micropiles, roadway excavation, repair retaining wall, repair viaduct, restore drainage systems, erosion control and additional work as necessary.
Location DescriptionIn Mendocino Bounty near Rockport from 9 miles South of Juan Creek Bridge to Juan Creek Bridge.
QA Service Level1 (Verified on 04/25/2024)

Sample Information

Sample Taken Date10/18/2024 Sample Unique Key42
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing10/24/2024
Sample typeQuality Assurance A brief description of the sample#6 Lenton Form Saver Coupler
The quantity of what the sample constitutesna From where was the sample collectedJob Site
First name of sampler or witnessed byna Last name of sampler or witnessed byna
Title of sampler Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameLenton Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeSMTL TM5 - Couplers Production or Authorization TestingProduction Testing
Service or UltimateService Material Standard CodeASTM A706
Material Grade60 Rebar ManufacturerNucor
Coupler ManufacturerLenton Intermediate Assembler or Fabricator
Rebar Size#6 Coupler ModelLenton Form Saver
Coating StandardsASTM A775 epoxy Shape of RebarStraight
Rebar Hoop Diameter Rebar Hoop Fabricator
Coupler Component Heat/Lot Number(s)M0145 Rebar Heat Number(s)1202061841
Rebar Size 2 Coupler Unique IDST-17-05

Test Details

DIME Sample ID: 2024-10-18-42
DIME Test ID: 2024-10-18-42-1
Testing Lab: Kleinfelder, Incorporated - Sacramento
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Test Release Date: 2024-10-29

Test Results


Number of Samples: 4
Input Type: Calculated
Tester's full name: K. DeSouza
Date of test: 10/29/2024
UTM: NA
Halo ID: na
Temperature: 72 f
NumSampleMfg. Lot Number(s)SizeArea (sqin)Slip (inch)Peak Load (lbf)Peak Stress (psi)CommentsTested By
11M014560.440.0013778086000naKD
22M014560.4403998091000naKD
33M014560.4403968090000naKD
44M014560.4403985090500naKD

General comments (publicly viewable) (Max 1000 characters): Service

Test was verified on 10/29/2024