Summary for Test 2024-10-10-19-1

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 215348
DEA: 060U4204
EFIS: 0616000004
DIST-CO-RTE-PM06-FRE-99-R4.9/11.6
Award Date02/25/2021
Closeout Date12/02/2025
Work DescriptionCONSTRUCT CRCP, PLACE HMA, AND ROADWAY EXCAVATION.
Location DescriptionFRESNO COUNTY IN AND NEAR SELMA AND FOWLER FROM MCCALL AVENUE UNDERCROSSING TO 0.5 MILE NORTH OF MERCED STREET UNDERCROSSING
QA Service Level1 (Verified on 12/07/2020)

Sample Information

Sample Taken Date10/10/2024 Sample Unique Key19
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing10/11/2024
Sample typeQuality Control A brief description of the sample4X8 Concrete Cylinders
The quantity of what the sample constitutes5 From where was the sample collectedJob Site
First name of sampler or witnessed bySok Last name of sampler or witnessed byThun
Title of samplerCT ASR Telephone number of sampler5592402198
Laboratory sample identificationMix NCT09064 Linked DIME Sample ID
The fabricator/manufacturer/facility nameSecurity Paving Company Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberNCT09064
The truck number from where the sample was collectedLoad 2 The batch plant ticket number from where the sample was collected1364893
Concrete batch plant111 The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedRTE 99, Median CIDH, STA 257+50 Where the material sample would have been placed if not sampledUnknown
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2024-10-10-19
DIME Test ID: 2024-10-10-19-1
Testing Lab: CT D06 - Millbrook Field Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2024-10-16

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Tomas Silva
Date of test: 10/16/2024
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 50570 lb
Maximum load on cylinder 2: 50710 lb
Maximum load on cylinder 3: 48230 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 6 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 4023.1 psi
Compressive strength of cylinder 2: 4034.2 psi
Compressive strength of cylinder 3: 3836.9 psi
Compressive strength (to nearest 10 psi): 3960 psi
General comments (publicly viewable) (Max 1000 characters): required strength 4000 @28 day

Test was verified on 10/16/2024