Summary for Test 2017-06-20-9-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 210871
DEA: 044G4604
EFIS: 0412000480
DIST-CO-RTE-PM04-MRN-101-1.5/14.0
Award Date01/28/2016
Closeout Date10/17/2019
Work DescriptionREMOVE EXISTING AND CONSTRUCT NEW BRIDGE RAILINGS.
Location DescriptionIN MARIN COUNTY, AT VARIOUS LOCATION, FROM SPENCER AVE OVERCROSSING TO NORTH BRANCHGALLINAS CREEK BRIDGE
QA Service Level1 (Verified on 01/12/2016)

Sample Information

Sample Taken Date06/20/2017 Sample Unique Key9
Will the laboratory/organization for which you are a member perform testing on this material sample?No Date that the sample was received by the laboratory/organization performing the testing07/28/2017
Sample typeQuality Assurance A brief description of the sample6x12 concrete cylinders
The quantity of what the sample constitutes90 Cy From where was the sample collectedJob Site
First name of sampler or witnessed byHarry Last name of sampler or witnessed bySuryantoro
Title of samplerASR AND SR Telephone number of sampler1-707-333-4263
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameShamrock Materials Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameSpencer Ave OC

Material Information

Material TypeConcrete The concrete mix design number4201a
The truck number from where the sample was collected1208 The batch plant ticket number from where the sample was collected155248
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedtruck chute Where the material sample would have been placed if not sampledOverhang Deck
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2017-06-20-9
DIME Test ID: 2017-06-20-9-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2017-08-09

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Bang
Date of test: 08/09/2017
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 197025 lb
Maximum load on cylinder 2: 202766 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 50 days
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 6922.9 psi
Compressive strength of cylinder 2: 7147.2 psi
Compressive strength (to nearest 10 psi): 7040 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Partner Data Point File
Test graph for Cylinder Code 1 of 2

Source: Partner Data Point File
Test graph for Cylinder Code 2 of 2

Test was verified on 8/9/2017