Summary for Test 2024-05-02-70-1

Test performed: ASTM C39-18

Project Information

Project IdentifiersProject ID: 214345
DEA: 120P94U4
EFIS: 1217000076
DIST-CO-RTE-PM12-ORA-133-3.2/R4.1
Award Date02/23/2021
Closeout DateNot set
Work DescriptionROADWAY WIDENING, RESTRIPING AND DRAINAGE WORK.
Location DescriptionORANGE COUNTY IN THE CITY OF LAGUNA BEACH FROM 0.2 MILE SOUTH OF EL TORO ROAD TO ROUTE 73/133 SEPARATION
QA Service Level1 (Verified on 12/10/2020)

Sample Information

Sample Taken Date05/02/2024 Sample Unique Key70
Date that the sample was received by the laboratory/organization performing the testing05/03/2024 Sample typeQuality Control
A brief description of the samplestructural concrete The quantity of what the sample constitutes2 cylinders
From where was the sample collectedJob Site First name of sampler or witnessed byRobert
Last name of sampler or witnessed byCota Title of sampler
Telephone number of sampler Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameCemex Irvine
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure name
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number1610838
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected31185609
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedSR133/73 Laguna Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2024-05-02-70
DIME Test ID: 2024-05-02-70-1
Testing Lab: Sequoia Consultants
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2024-05-31

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: John Romero
Date of test: 05/30/2024
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Maximum load on cylinder 1: 153160 lb
Maximum load on cylinder 2: 145860 lb
Type of fracture pattern of cylinder 1: 5
Type of fracture pattern of cylinder 2: 5
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength (to nearest 10 psi): 5290 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 5/31/2024 ✔