Summary for Test 2017-06-14-8-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 210735
DEA: 071193U4
EFIS: 0713000007
DIST-CO-RTE-PM07-LA-10-37.2/42.4
Award Date11/16/2015
Closeout Date07/11/2022
Work DescriptionCONSTRUCT HOV LANES, WIDEN BRIDGES, AND REALIGN RAMPS.
Location DescriptionIN LA COUNTY FROM CITRUS STREET IN WEST COVINA TO ROUTE 57 IN POMONA
QA Service Level1 (Verified on 03/07/2016)

Sample Information

Sample Taken Date06/14/2017 Sample Unique Key8
Date that the sample was received by the laboratory/organization performing the testingNot set Sample typeVerification
A brief description of the sample6x12 concrete cylinders The quantity of what the sample constitutes2 cylinders
From where was the sample collectedFabricator First name of sampler or witnessed byDavid
Last name of sampler or witnessed byWeeks Title of samplerCT METS QA INSPECTOR
Telephone number of sampler951-258-8382 Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameOLDCASTLE PRECAST PERRIS
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifierGirder B2 Structure nameGirder B2
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberUV-273
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected56182
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedCasting Bed A4 Where the material sample would have been placed if not sampledGirder B2
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2017-06-14-8
DIME Test ID: 2017-06-14-8-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2017-06-21

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Jose Guzman
Date of test: 06/21/2017
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.02 in
Maximum load on cylinder 1: 254360 lb
Maximum load on cylinder 2: 248210 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: no data
Age of specimen: 7 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.46 in^2
Compressive strength of cylinder 1: 8937.5 psi
Compressive strength of cylinder 2: 8721.4 psi
Compressive strength (to nearest 10 psi): 8830 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 6/21/2017 ✔