Summary for Test 2023-12-21-26-1

Test performed: ASTM C39-18

Project Information

Project IdentifiersProject ID: 994327
DEA: 081G4704
EFIS: 0816000001
DIST-CO-RTE-PM08-RIV-74-3.1/53.5
Award Date04/06/2023
Closeout Date10/05/2026
Work DescriptionSTRUCTURAL CONC BR, CONC SLAB, HMA (TYPE A), ALT CRASH CUSHION SYSTEM.
Location DescriptionRIVERSIDE COUNTY NEAR LAKE ELSINORE AT MORRILL CANYON BRIDGE AND NEAR HEMET AT STRAWBERRY CREEK BRIDGE.
QA Service Level1 (Verified on 06/08/2023)

Sample Information

Sample Taken Date12/21/2023 Sample Unique Key26
Date that the sample was received by the laboratory/organization performing the testing12/22/2023 Sample typeQuality Control
A brief description of the samplestructural concrete The quantity of what the sample constitutes2 cylinders
From where was the sample collectedJob Site First name of sampler or witnessed byRonald
Last name of sampler or witnessed byChairez Title of sampler
Telephone number of sampler Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameRobertson Ready Mix Hemet
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure name
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberSC675B34
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected587221
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedRetaining wall footing Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-12-21-26
DIME Test ID: 2023-12-21-26-1
Testing Lab: Sequoia Consultants
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2024-02-29

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Gavin Hernandez
Date of test: 01/18/2024
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Maximum load on cylinder 1: 147780 lb
Maximum load on cylinder 2: 139670 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength (to nearest 10 psi): 5080 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 2/29/2024 ✔