Summary for Test 2023-11-08-30-1
Test performed: ASTM C39-21Project Information
Project Identifiers | Project ID: 994554 DEA: 032G7304 EFIS: 0322000152 |
---|---|
DIST-CO-RTE-PM | 03-SAC-5-0.0/3.6 |
Award Date | 04/26/2023 |
Closeout Date | Not set |
Work Description | REPLACE CONCRETE SLABS WITH INDIVIDUAL PRECAST CONCRETE SLABS. |
Location Description | SACRAMENTO COUNTY NEAR MOKELUMNE CITY FROM SACRAMENTO COUNTY LINE TO 0.5 MILE NORTH OF DIERSSEN ROAD OVERCROSSING |
QA Service Level | 1 (Verified on 05/15/2023) |
Sample Information
Sample Taken Date | 11/08/2023 | Sample Unique Key | 30 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 11/08/2023 |
Sample type | Quality Control | A brief description of the sample | 1 CY of Concrete for Testing |
The quantity of what the sample constitutes | 1 CY of Concrete for Testing | From where was the sample collected | Fabricator |
First name of sampler or witnessed by | Mark Patrick | Last name of sampler or witnessed by | Baddu |
Title of sampler | Telephone number of sampler | ||
Laboratory sample identification | Linked DIME Sample ID | ||
The fabricator/manufacturer/facility name | Con-Fab California, LLC | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | K85CP1L |
---|---|---|---|
The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 9767 | |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | Bed DELTA, 7th Truck | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2023-11-08-30
DIME Test ID: 2023-11-08-30-1
Testing Lab: Con-Fab California Corporation - Lathrop
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-11-09
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Ferdinand Rosal
Date of test: 11/09/2023
Capped in accordance with?: no data
Apparent mass of submerged cylinder 1: 8.55 lb
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 58220 lb
Maximum load on cylinder 2: 58775 lb
Maximum load on cylinder 3: 62840 lb
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 4
Type of fracture pattern of cylinder 3: 5
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 1 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.56 in^2
Cross sectional area of cylinder 2: 12.56 in^2
Cross sectional area of cylinder 3: 12.56 in^2
Compressive strength (to nearest 10 psi): 4770 psi
Serial number of delivery ticket, if available: no data
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 11/9/2023 ✔