Summary for Test 2017-03-11-4-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 210695
DEA: 080K2924
EFIS: 0812000099
DIST-CO-RTE-PM08-SBD-10-32.9/R37.4
Award Date10/30/2015
Closeout Date08/08/2018
Work DescriptionREPLACE EXISTING (PCCP) WITH (RSCP).
Location DescriptionIN/NEAR REDLANDS FROM 0.2 MILE W/O FORD STREET TO 0.4 MILE E/O LIVEOAK CANYON ROAD.
QA Service Level1 (Verified on 10/19/2015)

Sample Information

Sample Taken Date03/11/2017 Sample Unique Key4
Date that the sample was received by the laboratory/organization performing the testing03/13/2017 Sample typeQuality Control
A brief description of the sample6x12 The quantity of what the sample constitutes6
From where was the sample collectedJob Site First name of sampler or witnessed byrma
Last name of sampler or witnessed byrma Title of samplerUnknown
Telephone number of samplerUnknown Laboratory sample identification945-19-4
Linked DIME Sample IDUnknown The fabricator/manufacturer/facility nameramco
Transportation Laboratory (TL) Number19-4 Inspector Lot Number from the Transportation Laboratory (TL) FormUnknown
Structure unique identifier10 WB LN2 778 30 TO 763 45 Structure name10WB LN2 755 15 TO 733 50
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numbercts 30 ram
The truck number from where the sample was collectedUnknown The batch plant ticket number from where the sample was collectednp
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectednp Where the material sample would have been placed if not sampledUnknown
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2017-03-11-4
DIME Test ID: 2017-03-11-4-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2017-03-20

Test Results


Unit system used?: US Units
Number of specimens: 6
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 03/18/2017
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.03 in
Average diameter of cylinder 2: 6.03 in
Average diameter of cylinder 3: 6.02 in
Average diameter of cylinder 4: 6.03 in
Average diameter of cylinder 5: 6.03 in
Average diameter of cylinder 6: 6.03 in
Maximum load on cylinder 1: 93000 lb
Maximum load on cylinder 2: 92870 lb
Maximum load on cylinder 3: 93210 lb
Maximum load on cylinder 4: 93710 lb
Maximum load on cylinder 5: 90710 lb
Maximum load on cylinder 6: 92220 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 1
Type of fracture pattern of cylinder 4: 2
Type of fracture pattern of cylinder 5: 1
Type of fracture pattern of cylinder 6: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: no data
Correction factor for cylinder 3: no data
Correction factor for cylinder 4: no data
Correction factor for cylinder 5: no data
Correction factor for cylinder 6: no data
Age of specimen: 7 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.56 in^2
Cross sectional area of cylinder 2: 28.56 in^2
Cross sectional area of cylinder 3: 28.46 in^2
Cross sectional area of cylinder 4: 28.56 in^2
Cross sectional area of cylinder 5: 28.56 in^2
Cross sectional area of cylinder 6: 28.56 in^2
Compressive strength of cylinder 1: 3256.3 psi
Compressive strength of cylinder 2: 3251.8 psi
Compressive strength of cylinder 3: 3275.1 psi
Compressive strength of cylinder 4: 3281.2 psi
Compressive strength of cylinder 5: 3176.1 psi
Compressive strength of cylinder 6: 3229.0 psi
Compressive strength (to nearest 10 psi): 3240 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 3/20/2017 ✔