Summary for Test 2023-08-23-78-3

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 215445
DEA: 100X7504
EFIS: 1013000009
DIST-CO-RTE-PM10-ALP-4,88,89-var
Award Date03/18/2021
Closeout Date04/22/2025
Work DescriptionREPLACE BRIDGE RAIL, BARRIER SLAB AND GUARDRAIL.
Location DescriptionALPINE COUNTY AT VARIOUS LOCATIONS
QA Service Level1 (Verified on 02/01/2021)

Sample Information

Sample Taken Date08/23/2023 Sample Unique Key78
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing08/24/2023
Sample typeQuality Assurance A brief description of the sampleFiber Deck Mix
The quantity of what the sample constitutes(3) 4x8 Test Cylinders From where was the sample collectedJob Site
First name of sampler or witnessed byRamneet Last name of sampler or witnessed bySidhu
Title of samplerFIELD INSPECTOR Telephone number of sampler5308124294
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameNot Provided Transportation Laboratory (TL) NumberTL502 79400
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier31-0028
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberD673A
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedNot Provided
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedTransit Truck Chute Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-08-23-78
DIME Test ID: 2023-08-23-78-3
Testing Lab: CT D10 - Stockton Field Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2023-10-04

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Tim Trefz
Date of test: 10/04/2023
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 70480 lb
Maximum load on cylinder 2: 71260 lb
Maximum load on cylinder 3: 72130 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 42 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 5607.0 psi
Compressive strength of cylinder 2: 5669.1 psi
Compressive strength of cylinder 3: 5738.3 psi
Compressive strength (to nearest 10 psi): 5670 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 10/4/2023