Summary for Test 2023-09-15-58-3

Test performed: ASTM C39-18

Project Information

Project IdentifiersProject ID: 994309
DEA: 033H5404
EFIS: 0318000012
DIST-CO-RTE-PM03-BUT-70-46.0/47.0
Award Date02/10/2023
Closeout Date07/31/2026
Work DescriptionRAISE ALIGNMENT, PLACE HMA, STRUCTURAL CONCRETE & BRIDGE RAIL.
Location DescriptionBUTTE COUNTY NEAR PARADISE FROM 0.8 MILE WEST OF SHADY REST AREA TO 0.2 MILE EAST OF SHADY REST AREA
QA Service Level1 (Verified on 10/04/2022)

Sample Information

Sample Taken Date09/15/2023 Sample Unique Key58
Date that the sample was received by the laboratory/organization performing the testing09/18/2023 Sample typeDepartment Acceptance
A brief description of the samplePCC The quantity of what the sample constitutes9 cy
From where was the sample collectedJob Site First name of sampler or witnessed byMatt
Last name of sampler or witnessed byCrete Title of samplerStructure Rep
Telephone number of sampler15306823759 Laboratory sample identification23-155
Linked DIME Sample ID The fabricator/manufacturer/facility nameShasta RM
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier12-0207 Structure name
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberCT-675BD-SEA
The truck number from where the sample was collected41 The batch plant ticket number from where the sample was collected80929
Concrete batch plantShasta RM The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedStage-2 Deck Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-09-15-58
DIME Test ID: 2023-09-15-58-3
Testing Lab: CT D03 - Chico Field Laboratory
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-09-25

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Brad McKeehan
Date of test: 09/22/2023
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 43440 lb
Maximum load on cylinder 2: 42000 lb
Maximum load on cylinder 3: 43150 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 7 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 3455.8 psi
Compressive strength of cylinder 2: 3341.3 psi
Compressive strength of cylinder 3: 3432.8 psi
Compressive strength (to nearest 10 psi): 3410 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 9/25/2023 ✔