Summary for Test 2023-08-14-38-1
Test performed: ASTM C39-21Project Information
| Project Identifiers | Project ID: 994441 DEA: 081A8304 EFIS: 0800000579 COOP: 081746 |
|---|---|
| DIST-CO-RTE-PM | 08--- |
| Award Date | 10/05/2022 |
| Closeout Date | Not set |
| Work Description | Widening the existing Cedar Avenue overcrossing (OC) from 6 to 10 lanes, replacing the Union Pacific Railroad overhead (OH), widening Cedar Avenue from 4 to 6 through lanes, and realigning and/or widening the interchange entrance and exit ramps |
| Location Description | At the Interstate 10 (I-10) Cedar Avenue Interchange from PM 17.8 to 19.3 in the County of San Bernardino (County) |
| QA Service Level | 2 (Verified on 12/13/2022) |
Sample Information
| Sample Taken Date | 08/14/2023 | Sample Unique Key | 38 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 08/15/2023 |
| Sample type | Quality Control | A brief description of the sample | 1 CF of Concrete for Testing |
| The quantity of what the sample constitutes | 1 CF of Concrete for Testing | From where was the sample collected | Manufacturer |
| First name of sampler or witnessed by | PJ | Last name of sampler or witnessed by | Wright |
| Title of sampler | Telephone number of sampler | ||
| Laboratory sample identification | Linked DIME Sample ID | ||
| The fabricator/manufacturer/facility name | Con-Fab California, LLC | Transportation Laboratory (TL) Number | |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
| Structure name | Bid Item | Not set |
Material Information
| Material Type | Concrete | The concrete mix design number | VER-98LV |
|---|---|---|---|
| The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 9362 | |
| Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
| A detailed description of where the material sample was collected | Bed 1B, 3rd Truck | Where the material sample would have been placed if not sampled | |
| From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2023-08-14-38
DIME Test ID: 2023-08-14-38-1
Testing Lab: Con-Fab California Corporation - Lathrop
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-08-16
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Ferdinand Rosal
Date of test: 08/15/2023
Capped in accordance with?: no data
Apparent mass of submerged cylinder 1: 8.98 lb
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 100730 lb
Maximum load on cylinder 2: 96400 lb
Maximum load on cylinder 3: 97355 lb
Type of fracture pattern of cylinder 1: 5
Type of fracture pattern of cylinder 2: 5
Type of fracture pattern of cylinder 3: 5
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 1 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.56 in^2
Cross sectional area of cylinder 2: 12.56 in^2
Cross sectional area of cylinder 3: 12.56 in^2
Compressive strength (to nearest 10 psi): 7820 psi
Serial number of delivery ticket, if available: no data
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 8/16/2023 ✔