Summary for Test 2023-06-14-69-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 214337
DEA: 080E33U4
EFIS: 0817000075
DIST-CO-RTE-PM08-SBD-115-R7.3/R10.0
Award Date04/26/2021
Closeout DateNot set
Work DescriptionADD WB AUX & EB DECEL LANES, WIDEN I15 SW CONNECT,RAMPS/BRDG
Location DescriptionSAN BERNARDINO COUNTY IN ONTARIO FROM 0.2 MILE WEST OF CUCAMONGA CREEK BRIDGE TO MILLIKEN AVENUE
QA Service Level1 (Verified on 06/23/2021)

Sample Information

Sample Taken Date06/14/2023 Sample Unique Key69
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing05/27/2022
Sample typeQuality Assurance A brief description of the sample4x8 cylinder
The quantity of what the sample constitutes6 cylinder From where was the sample collectedJob Site
First name of sampler or witnessed byVictor Last name of sampler or witnessed byWami
Title of samplerASR Telephone number of sampler
Laboratory sample identification1040-614A Linked DIME Sample ID
The fabricator/manufacturer/facility nameBoral Transportation Laboratory (TL) Number1040-614A
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design numberSM445B37
The truck number from where the sample was collected1712 The batch plant ticket number from where the sample was collected7850790
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedPIER 2 AND 3 FOOTINGS Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-06-14-69
DIME Test ID: 2023-06-14-69-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-06-26

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Ali Rehman
Date of test: 06/21/2023
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 4.01 in
Average diameter of cylinder 2: 4.01 in
Maximum load on cylinder 1: 51720 lb
Maximum load on cylinder 2: 52890 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 7 days
Cross sectional area of cylinder 1: 12.63 in^2
Cross sectional area of cylinder 2: 12.63 in^2
Compressive strength of cylinder 1: 4095.0 psi
Compressive strength of cylinder 2: 4187.6 psi
Compressive strength (to nearest 10 psi): 4140 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 6/26/2023