Summary for Test 2022-12-23-26-1

Test performed: ASTM C39-21

Project Information

Project IdentifiersProject ID: 993279
DEA: 010E0904
EFIS: 0113000123
DIST-CO-RTE-PM01-MEN-20-33.3/34.4
Award Date05/06/2022
Closeout Date04/22/2026
Work DescriptionCONSTRUCT NEW BRIDGE, REMOVE TWO BRIDGES, EARTHWORK AND PAVING. (Bridge No. 10-0310)
Location DescriptionMENDOCINO COUNTY NEAR UKIAH FROM 0.3 MILE WEST OF RUSSIAN RIVER BRIDGE AND OVERHEAD TO 0.3 MILE EAST OF COUNTY ROAD 144
QA Service Level1 (Verified on 10/04/2021)

Sample Information

Sample Taken Date12/23/2022 Sample Unique Key26
Date that the sample was received by the laboratory/organization performing the testing12/24/2022 Sample typeQuality Assurance
A brief description of the sample4x8 concrete cylinders The quantity of what the sample constitutes10 cy
From where was the sample collectedJob Site First name of sampler or witnessed byRiley
Last name of sampler or witnessed byMelvin Title of sampler
Telephone number of sampler Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameNor-Cal
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier10-0310 Structure nameRussian River BOH
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number718034A
The truck number from where the sample was collected1 The batch plant ticket number from where the sample was collected43283
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedBack of Truck Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-12-23-26
DIME Test ID: 2022-12-23-26-1
Testing Lab: CT SC - 3667 - Redwood Valley/Fort Bragg
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-05-08

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Riley Melvin
Date of test: 01/20/2023
Capped in accordance with?: no data
Apparent mass of submerged cylinder 1: 9.15 lb
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 97010 lb
Maximum load on cylinder 2: 98010 lb
Maximum load on cylinder 3: 95710 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength (to nearest 10 psi): 7710 psi
Serial number of delivery ticket, if available: no data
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 5/8/2023 ✔