Summary for Test 2022-12-12-22-2

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 993301
DEA: 060U2804
EFIS: 0615000293
DIST-CO-RTE-PM06-TUL-245-1.4,4.2
Award Date01/03/2022
Closeout Date05/09/2025
Work DescriptionPRECAST PRESTRESSED CONCRETE BOX GIRDER AND SLAB, BRIDGE REMOVAL.
Location DescriptionTULARE COUNTY NEAR WOODLAKE AT YOKOHL CREEK BRIDGE AND AT KAWEAH RIVER BRIDGE
QA Service Level1 (Verified on 10/11/2021)

Sample Information

Sample Taken Date12/12/2022 Sample Unique Key22
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing12/24/2022
Sample typeQuality Assurance A brief description of the sampleType II Cement Concrete Agg 4x8 Cylinders
The quantity of what the sample constitutesBridge Deck Pour From where was the sample collectedJob Site
First name of sampler or witnessed byFares Last name of sampler or witnessed byThwabah
Title of samplerStructure Representative Telephone number of sampler5592875457
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameViking Ready Mix Visalia Shirk Rd Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure nameTul 245 Kaweah Bridge Deck Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberND14505
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected116206747
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collected4x8 Concrete Cylinders fabricated on job site Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-12-12-22
DIME Test ID: 2022-12-12-22-2
Testing Lab: CT D06 - Visalia Field Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2023-04-04

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Shoaib Ahmed
Date of test: 12/30/2022
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 49910 lb
Maximum load on cylinder 2: 47865 lb
Maximum load on cylinder 3: 47955 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 7 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength (to nearest 10 psi): 3860 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 4/4/2023