Summary for Test 2023-02-28-12-3

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 215620
DEA: 01436404
EFIS: 0100000193
DIST-CO-RTE-PM01-DN-101-35.8/36.5
Award Date07/11/2022
Closeout DateNot set
Work DescriptionDr. Fine Bridge Replacement
Location DescriptionDR. FINE BRIDGE REPLACEMENT FROM LAKE EARL DR TO S FRED D. HAIGHT DR ON HWY 101 ACROSS SMITH RIVER.
QA Service Level1 (Verified on 03/26/2021)

Sample Information

Sample Taken Date02/28/2023 Sample Unique Key12
Date that the sample was received by the laboratory/organization performing the testing02/28/2023 Sample typeQuality Assurance
A brief description of the sampleCIP Concrete The quantity of what the sample constitutes46 CY
From where was the sample collectedJob Site First name of sampler or witnessed byTance
Last name of sampler or witnessed bySingletary Title of samplerASR
Telephone number of sampler4074628500 Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameTidewater Starry pit
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) FormDS-0001
Structure unique identifier01-0041 Structure nameDr Fine Temporary Bridge
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberSR3-8CIDH
The truck number from where the sample was collected109 The batch plant ticket number from where the sample was collected57578
Concrete batch plantStary Plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedCHUTE FROM TRUCK Where the material sample would have been placed if not sampledTemp Abutment 1 RT CIDH
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-02-28-12
DIME Test ID: 2023-02-28-12-3
Testing Lab: CT D01 - District 1 Materials Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2023-03-28

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Leif Ayres
Date of test: 03/28/2023
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 195460 lb
Maximum load on cylinder 2: 215470 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 5
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.3 in^2
Cross sectional area of cylinder 2: 28.3 in^2
Compressive strength (to nearest 10 psi): 7260 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 3/28/2023 ✔