Summary for Test 2023-02-08-5-1

Test performed: ASTM C39-18

Project Information

Project IdentifiersProject ID: 993776
DEA: 040J3004
EFIS: 0413000433
DIST-CO-RTE-PM04-SON-1-26.7/27.1
Award Date07/08/2022
Closeout DateNot set
Work DescriptionCONSTRUCTING RETAINING WALL AND CONFINEMENT SYSTEM TO RESTORE SLIPOUT.
Location DescriptionSONOMA COUNTY NEAR JENNER FROM 0.3 MILE TO 0.7 MILE NORTH OF MEYERS GRADE ROAD
QA Service Level1 (Verified on 05/11/2022)

Sample Information

Sample Taken Date02/08/2023 Sample Unique Key5
Date that the sample was received by the laboratory/organization performing the testing02/24/2023 Sample typeQuality Assurance
A brief description of the sampleSoldier Pile Concrete Backfill Piles 119 The quantity of what the sample constitutes30 cy
From where was the sample collectedJob Site First name of sampler or witnessed byJohnathan
Last name of sampler or witnessed byLopez Title of samplerASR
Telephone number of sampler9515429238 Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameCanyon Rock
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier20-E0110 Structure nameSlidesville Retaining Wall
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number72203043F
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedTBD
Concrete batch plantForestville Canyon Rock The fabricator/manufacturer designation for the sampleConcrete Backfill Wet Hole
A detailed description of where the material sample was collectedChute Where the material sample would have been placed if not sampledSoldier Pile
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2023-02-08-5
DIME Test ID: 2023-02-08-5-1
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2023-02-16

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Nikhil Moon
Date of test: 02/15/2023
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 50200 lb
Maximum load on cylinder 2: 52650 lb
Maximum load on cylinder 3: 54785 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 7 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.57 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.57 in^2
Compressive strength of cylinder 1: 3993.6 psi
Compressive strength of cylinder 2: 4188.5 psi
Compressive strength of cylinder 3: 4358.4 psi
Compressive strength (to nearest 10 psi): 4180 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 2/16/2023 ✔