Summary for Test 2022-12-13-40-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 993776
DEA: 040J3004
EFIS: 0413000433
DIST-CO-RTE-PM04-SON-1-26.7/27.1
Award Date07/08/2022
Closeout DateNot set
Work DescriptionCONSTRUCTING RETAINING WALL AND CONFINEMENT SYSTEM TO RESTORE SLIPOUT.
Location DescriptionSONOMA COUNTY NEAR JENNER FROM 0.3 MILE TO 0.7 MILE NORTH OF MEYERS GRADE ROAD
QA Service Level1 (Verified on 05/11/2022)

Sample Information

Sample Taken Date12/13/2022 Sample Unique Key40
Date that the sample was received by the laboratory/organization performing the testing12/13/2022 Sample typeQuality Assurance
A brief description of the sample4x8 #9 concrete cylinders The quantity of what the sample constitutes9 concrete cylinders
From where was the sample collectedJob Site First name of sampler or witnessed byFabio
Last name of sampler or witnessed byLa Serna Title of samplerRE
Telephone number of sampler Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameAgronaut Constructors
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure name
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberSL-4700CG
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedSL-4700CG
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collected9 Concrete Cylinders Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-12-13-40
DIME Test ID: 2022-12-13-40-1
Testing Lab: CT HQ - Vallejo Field Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2022-12-22

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Nikhil Moon
Date of test: 12/13/2022
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 60250 lb
Maximum load on cylinder 2: 54030 lb
Maximum load on cylinder 3: 54150 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 7 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.566 in^2
Cross sectional area of cylinder 2: 12.566 in^2
Cross sectional area of cylinder 3: 12.566 in^2
Compressive strength (to nearest 10 psi): 4410 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 12/22/2022 ✔