Summary for Test 2022-12-17-7-1

Test performed: CTM 524-March 2013

Project Information

Project IdentifiersProject ID: 214524
DEA: 07304504
EFIS: 0714000067
DIST-CO-RTE-PM07-LA-57-R0.0/R4.5
Award Date06/11/2020
Closeout Date04/03/2025
Work DescriptionCONCRETE PAVEMENT, CONCRETE BARRIER, AND ELECTRICAL WORK.
Location DescriptionLOS ANGELES COUNTY IN DIAMOND BAR AND CITY OF INDUSTRY FROM ORANGE COUNTY LINE TO ROUTE 57/60 SEPARATION
QA Service Level1 (Verified on 08/12/2020)

Sample Information

Sample Taken Date12/17/2022 Sample Unique Key7
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing12/18/2022
Sample typeQuality Assurance A brief description of the sampleConcrete Beams JPCP-RSC
The quantity of what the sample constitutes10 Cubic Yards From where was the sample collectedJob Site
First name of sampler or witnessed byManuel Last name of sampler or witnessed byUy
Title of sampler Telephone number of sampler
Laboratory sample identification22-3185 Linked DIME Sample ID
The fabricator/manufacturer/facility namen/a Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberHE4X4B
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected13623
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedWheelbarrow Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-12-17-7
DIME Test ID: 2022-12-17-7-1
Testing Lab: Alta Vista Solutions - Whittier
Test Method: CTM 524-March 2013: Method of Test for Flexural Strength Of Rapid Strength Concrete
Test Release Date: 2022-12-21

Test Results


Number of specimens: 3
Does the testing machine measure load or stress on the beam specimen?: Load
Fracture initiates in the tension surface: Within the Middle Third of the Span Length
Fracture occurred at a capped section: No
Is a beam dimensional correction factor used?: No
Input Type: Calculated
Tester's full name: Nathan Ogbasellasie
Date of test: 12/20/2022
Identification number: 22-3185
Width of specimen: 6 inch
Width of specimen 2: 6 inch
Width of specimen 3: 6 inch
Depth of specimen: 6.0625 inch
Depth of specimen 2: 6.125 inch
Depth of specimen 3: 6.125 inch
Span length of specimen: 18 inch
Span length of specimen 2: 18 inch
Span length of specimen 3: 18 inch
Maximum load applied: 11279 lb
Maximum load applied 2: 11397 lb
Maximum load applied 3: 12167 lb
Curing history and apparent moisture condition of the specimen: Ok
If specimen was capped, ground or if leather shims were used: no
Defects in specimen, including numbers of beams discarded during test: no
Age of specimen: 3 days
Age of specimen in hours: no data
Modulus of rupture: 970 psi
Modulus of rupture 2: 960 psi
Modulus of rupture 3: 1020 psi
Modulus of rupture average: 980 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 12/21/2022