Summary for Test 2016-08-12-13-2

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 209139
DEA: 071170U4
EFIS: 0700000085
DIST-CO-RTE-PM07-LA-10-33.2/37.2
Award Date02/10/2014
Closeout Date03/01/2022
Work DescriptionCONSTRUCT HOV LANES, WIDEN BRIDGES, AND REALIGN RAMPS.
Location DescriptionLOS ANGELES COUNTY IN BALDWIN PARK AND WEST COVINA FROM 0.1 MILE WEST OF PUENTE AVENUE UNDERCROSSING TO 0.2 MILE EAST OF HOLLENBECK STREET UNDERCROSSING
QA Service Level1 (Verified on 05/06/2014)

Sample Information

Sample Taken Date08/12/2016 Sample Unique Key13
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing08/15/2016
Sample typeQuality Assurance A brief description of the sample6x12 concrete cylinders
The quantity of what the sample constitutes6 From where was the sample collectedJob Site
First name of sampler or witnessed byOSCAR Last name of sampler or witnessed byRODRIGUEZ
Title of samplerASR TEC Telephone number of samplerUnknown
Laboratory sample identification882-74A Linked DIME Sample IDUnknown
The fabricator/manufacturer/facility nameHolliday Upland Transportation Laboratory (TL) Number101083474A
Inspector Lot Number from the Transportation Laboratory (TL) FormUnknown Structure unique identifierUnknown
Structure nameUnknown

Material Information

Material TypeConcrete The concrete mix design numberCT1-C2400
The truck number from where the sample was collected100 The batch plant ticket number from where the sample was collected101083474
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedTRUCK Where the material sample would have been placed if not sampledHOLLENBECK AVE UC ALL ABUTMENTS APPROACH SLABS TYPE N
From Lot No.Unknown Bag Lot No.Unknown

Test Details

DIME Sample ID: 2016-08-12-13
DIME Test ID: 2016-08-12-13-2
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2016-09-09

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 09/09/2016
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 5.99 in
Average diameter of cylinder 2: 5.99 in
Maximum load on cylinder 1: 128740 lb
Maximum load on cylinder 2: 128850 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.18 in^2
Cross sectional area of cylinder 2: 28.18 in^2
Compressive strength of cylinder 1: 4568.5 psi
Compressive strength of cylinder 2: 4572.4 psi
Compressive strength (to nearest 10 psi): 4570 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 9/9/2016