Summary for Test 2022-06-26-1-1

Test performed: CTM 524-March 2013

Project Information

Project IdentifiersProject ID: 214493
DEA: 07311704
EFIS: 0715000013
DIST-CO-RTE-PM07-LA-134-0.0/R13.3
Award Date04/16/2020
Closeout Date07/09/2024
Work DescriptionCONCRETE SLAB REPLACEMENT, HMA PAVING, ELECTRICAL AND LANDSCAPE WORK.
Location DescriptionLOS ANGELES COUNTY IN LOS ANGELES, BURBANK, GLENDALE AND PASADENA FROM ROUTE 101/134 SEPARATION TO JUNCTION OF ROUTE 210/710
QA Service Level1 (Verified on 04/15/2020)

Sample Information

Sample Taken Date06/26/2022 Sample Unique Key1
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing06/26/2022
Sample typeDepartment Acceptance A brief description of the sample6x6x21 beams
The quantity of what the sample constitutes130 CY From where was the sample collectedJob Site
First name of sampler or witnessed byPaul Last name of sampler or witnessed byPastora
Title of samplerRMA QC Telephone number of sampler
Laboratory sample identification22-1544 Linked DIME Sample ID
The fabricator/manufacturer/facility namePeterson Chase Transportation Laboratory (TL) Number062622
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberNA
The truck number from where the sample was collected2122 The batch plant ticket number from where the sample was collectedNA
Concrete batch plantPeterson Chase The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedCHUTE FROM TRUCK Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-06-26-1
DIME Test ID: 2022-06-26-1-1
Testing Lab: CT D07 - Materials Field Laboratory, Unit 1953
Test Method: CTM 524-March 2013: Method of Test for Flexural Strength Of Rapid Strength Concrete
Test Release Date: 2022-06-29

Test Results


Number of specimens: 3
Does the testing machine measure load or stress on the beam specimen?: Load
Fracture initiates in the tension surface: Within the Middle Third of the Span Length
Fracture occurred at a capped section: No
Is a beam dimensional correction factor used?: No
Input Type: Measured
Tester's full name: Robert Achuela
Date of test: 06/29/2022
Identification number: 22-1544
Width of specimen: 6 inch
Width of specimen 2: 6 inch
Width of specimen 3: 6 inch
Depth of specimen: 6.125 inch
Depth of specimen 2: 6.125 inch
Depth of specimen 3: 6.125 inch
Span length of specimen: 18 inch
Span length of specimen 2: 18 inch
Span length of specimen 3: 18 inch
Maximum load applied: 9007 lb
Maximum load applied 2: 9501 lb
Maximum load applied 3: 8988 lb
Curing history and apparent moisture condition of the specimen: 75 F saturated condition
If specimen was capped, ground or if leather shims were used: No
Defects in specimen, including numbers of beams discarded during test: None
Age of specimen: 3 days
Age of specimen in hours: no data
Modulus of rupture: 760 psi
Modulus of rupture 2: 800 psi
Modulus of rupture 3: 750 psi
Modulus of rupture average: 770 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 6/29/2022