Summary for Test 2016-06-04-2-1

Test performed: ASTM C109-11

Project Information

Project IdentifiersProject ID: 210864
DEA: 041SS034
EFIS: 0400020869
DIST-CO-RTE-PM04-ALA-580-R4.9/R5.6
Award Date12/18/2015
Closeout Date12/21/2017
Work DescriptionCONSTRUCT SOLDIER PILE WALL, AND RECONSTRUCTION OF LANES & SOULDERS
Location DescriptionIN ALAMEDA COUNTY, ON WESTBOUND OF ROUTE 580. AT PM 5.0
QA Service Level1 (Verified on 10/28/2015)

Sample Information

Sample Taken Date06/04/2016 Sample Unique Key2
Date that the sample was received by the laboratory/organization performing the testing06/10/2016 Sample typeVerification
A brief description of the sample2x2 cubes The quantity of what the sample constitutes3 cubes
From where was the sample collectedJob Site First name of sampler or witnessed bySandhu
Last name of sampler or witnessed bykharakbir Title of samplerUnknown
Telephone number of samplerUnknown Laboratory sample identificationUnknown
Linked DIME Sample IDUnknown The fabricator/manufacturer/facility nameUnknown
Transportation Laboratory (TL) Number155542 Inspector Lot Number from the Transportation Laboratory (TL) FormUnknown
Structure unique identifierNot set Structure nameNot set
Bid ItemNot set

Material Information

Material TypeCementitious Brandquikrete
Millunknown Type of Cementitious MaterialType II/V Cement

Test Details

DIME Sample ID: 2016-06-04-2
DIME Test ID: 2016-06-04-2-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C109-11: Compressive Strength of Hydraulic Cement Mortars (Using 2-in. or [50mm] Cube Specimens)
Test Release Date: 2016-07-11

Test Results


Will control cubes be used per ASTM C311?: no
Input Type: Measured
Tester's full name: Mike Mullins
Date of test: 07/05/2016
Age of specimen: 31 days
The amount of flow (In percent): 1 %
The amount of water used (In percent): 100 %
Maximum load of 1st specimen (lb): 17252 lb
Maximum load of 2nd specimen (lb): 16287 lb
Maximum load of 3rd specimen (lb): 17835 lb
Cross sectional area loaded of 1st specimen (sq. inch): 4 in^2
Cross sectional area loaded of 2nd specimen (sq. inch): 4 in^2
Cross sectional area loaded of 3rd specimen (sq. inch): 4 in^2
Compressive strength of 1st specimen (psi): 4313 psi
Compressive strength of 2nd specimen (psi): 4071.75 psi
Compressive strength of 3rd specimen (psi): 4458.75 psi
Average Compressive strength (to nearest 10 psi): 4281 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 7/11/2016 ✔