Summary for Test 2022-05-10-37-2

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 214663
DEA: 081F7304
EFIS: 0815000034
DIST-CO-RTE-PM08-SBD-215-2.7
Award Date03/04/2021
Closeout Date06/03/2025
Work DescriptionREPLACE CONCRETE BRIDGE, PLACE CONCRETE PCPS GIRDERS AND HMA.
Location DescriptionSAN BERNARDINO COUNTY IN COLTON AT WASHINGTON STREET OVERCROSSING
QA Service Level1 (Verified on 02/24/2021)

Sample Information

Sample Taken Date05/10/2022 Sample Unique Key37
Date that the sample was received by the laboratory/organization performing the testing05/11/2022 Sample typeQuality Control
A brief description of the sample6x12 The quantity of what the sample constitutes4
From where was the sample collectedJob Site First name of sampler or witnessed byNathan
Last name of sampler or witnessed byOGBASELLASIE Title of samplerQA Inspector
Telephone number of sampler Laboratory sample identification1037-512
Linked DIME Sample ID The fabricator/manufacturer/facility nameNA
Transportation Laboratory (TL) Number1 Inspector Lot Number from the Transportation Laboratory (TL) Form
Structure unique identifier Structure name
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number1611614
The truck number from where the sample was collected10067790 The batch plant ticket number from where the sample was collected52770088
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedNB 215 Washington Exit RW 105 load 3 Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-05-10-37
DIME Test ID: 2022-05-10-37-2
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2022-06-10

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Jose Guzman
Date of test: 06/07/2022
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 5.97 in
Average diameter of cylinder 2: 5.97 in
Maximum load on cylinder 1: 153980 lb
Maximum load on cylinder 2: 154885 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 28 days
Cross sectional area of cylinder 1: 27.99 in^2
Cross sectional area of cylinder 2: 27.99 in^2
Compressive strength of cylinder 1: 5501.3 psi
Compressive strength of cylinder 2: 5533.6 psi
Compressive strength (to nearest 10 psi): 5520 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 6/10/2022 ✔