Summary for Test 2022-01-31-6-6
Test performed: ASTM C39-21Project Information
| Project Identifiers | Project ID: 214991 DEA: 044G2104 EFIS: 0412000310 |
|---|---|
| DIST-CO-RTE-PM | 04-NAP-121-0.5/1 |
| Award Date | 05/19/2021 |
| Closeout Date | 10/09/2024 |
| Work Description | WIDEN ROADWAY WITH HMA & REPLACE CULVERT WITH STRUCTURAL CONC BRIDGE. |
| Location Description | NAPA COUNTY NEAR NAPA FROM 0.2 MILE SOUTH TO 0.3 MILE NORTH OF HUICHICA CREEK BRIDGE |
| QA Service Level | 1 (Verified on 10/19/2020) |
Sample Information
| Sample Taken Date | 01/31/2022 | Sample Unique Key | 6 |
|---|---|---|---|
| Date that the sample was received by the laboratory/organization performing the testing | 02/01/2022 | Sample type | Quality Control |
| A brief description of the sample | 1CY of Concrete taken from middle of batching | The quantity of what the sample constitutes | 1 CY of Concrete for Testing |
| From where was the sample collected | Manufacturer | First name of sampler or witnessed by | Mark Patrick |
| Last name of sampler or witnessed by | Baddu | Title of sampler | |
| Telephone number of sampler | Laboratory sample identification | ||
| Linked DIME Sample ID | The fabricator/manufacturer/facility name | Con-Fab California, LLC | |
| Transportation Laboratory (TL) Number | Inspector Lot Number from the Transportation Laboratory (TL) Form | ||
| Structure unique identifier | Structure name | ||
| Bid Item | Not set |
Material Information
| Material Type | Concrete | The concrete mix design number | VER-90LV |
|---|---|---|---|
| The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | 4399 | |
| Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
| A detailed description of where the material sample was collected | Bed 2, 2nd Truck | Where the material sample would have been placed if not sampled | |
| From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2022-01-31-6
DIME Test ID: 2022-01-31-6-6
Testing Lab: Con-Fab California Corporation - Lathrop
Test Method: ASTM C39-21: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2022-03-03
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Ferdinand Rosal
Date of test: 02/28/2022
Capped in accordance with?: no data
Apparent mass of submerged cylinder 1: 8.89 lb
Average diameter of cylinder 1: 4.00 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.00 in
Maximum load on cylinder 1: 124300 lb
Maximum load on cylinder 2: 122000 lb
Maximum load on cylinder 3: 125000 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.56 in^2
Cross sectional area of cylinder 2: 12.56 in^2
Cross sectional area of cylinder 3: 12.56 in^2
Compressive strength (to nearest 10 psi): 9850 psi
Serial number of delivery ticket, if available: no data
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 3/3/2022 ✔