Summary for Test 2021-06-03-1-1

Test performed: ASTM C39-18

Project Information

Project IdentifiersProject ID: 215075
DEA: 060Q9104
EFIS: 0614000005
DIST-CO-RTE-PM06-TUL-99-19.2/19.8
Award Date09/25/2020
Closeout Date05/11/2023
Work DescriptionBRIDGE DECK AND OUTSIDE GIRDER REPLACEMENT.
Location DescriptionTULARE COUNTY NEAR TIPTON FROM 0.3 MILE SOUTH TO 0.3 MILE NORTH OF AVENUE 152 OVERCROSSING
QA Service Level1 (Verified on 07/28/2020)

Sample Information

Sample Taken Date06/03/2021 Sample Unique Key1
Date that the sample was received by the laboratory/organization performing the testing06/04/2021 Sample typeQuality Assurance
A brief description of the sample(2) 6"x12" Cylinders The quantity of what the sample constitutes(2) 6"x12" Cylinders
From where was the sample collectedFabricator First name of sampler or witnessed byRigoberto
Last name of sampler or witnessed byMarin Title of samplerAMR
Telephone number of sampler9515000685 Laboratory sample identification
Linked DIME Sample ID The fabricator/manufacturer/facility nameCon-Fab California, LLC
Transportation Laboratory (TL) Number Inspector Lot Number from the Transportation Laboratory (TL) FormL133-065-21
Structure unique identifier Structure name
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberSCC S9 8 0F
The truck number from where the sample was collected2 The batch plant ticket number from where the sample was collected1283
Concrete batch plantSPC onsite batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedAt pour location Where the material sample would have been placed if not sampledGirder
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2021-06-03-1
DIME Test ID: 2021-06-03-1-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2021-07-07

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 07/01/2021
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.02 in
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Maximum load on cylinder 1: 281040 lb
Maximum load on cylinder 2: 290810 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.46 in^2
Compressive strength of cylinder 1: 9906.2 psi
Compressive strength of cylinder 2: 10218.2 psi
Compressive strength (to nearest 10 psi): 10060 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 7/7/2021 ✔