Summary for Test 2015-04-28-4-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 600
DEA: 02378904
EFIS: 0200000288
DIST-CO-RTE-PM02-SHA-5-R63.2/R65.8
Award Date09/25/2009
Closeout Date12/01/2021
Work DescriptionBRIDGE REPLACEMENT
Location DescriptionIN SHASTA COUNTYNEAR LAKEHEAD FROM 0.3 KM NORTH OF ANTLER SUMMIT OVERCROSSING TO 0.5 KM NORTH OFANTLER UNDERPASS
QA Service Level1 (Verified on 03/19/2012)

Sample Information

Sample Taken Date04/28/2015 Sample Unique Key4
Date that the sample was received by the laboratory/organization performing the testing04/28/2015 Sample typePer Request
A brief description of the sample6x12 concrete cylinders The quantity of what the sample constitutes2 cylinders
From where was the sample collectedOther First name of sampler or witnessed byLarry
Last name of sampler or witnessed byMcCrum Title of samplerUnknown
Telephone number of samplerUnknown Laboratory sample identificationUnknown
Linked DIME Sample IDUnknown The fabricator/manufacturer/facility nameTranslab
Transportation Laboratory (TL) Number95651 Inspector Lot Number from the Transportation Laboratory (TL) FormUnknown
Structure unique identifierUnknown Structure nameUnknown
Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design numberClean 1
The truck number from where the sample was collectedUnknown The batch plant ticket number from where the sample was collectedzzzzzzzzzzzzzzzzzzzz
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedTranslab Where the material sample would have been placed if not sampledNot set
From Lot No.Not set Bag Lot No.Not set

Test Details

DIME Sample ID: 2015-04-28-4
DIME Test ID: 2015-04-28-4-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2015-06-02

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Mullins
Date of test: 05/26/2015
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 281567 lb
Maximum load on cylinder 2: 238091 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength of cylinder 1: 9924.8 psi
Compressive strength of cylinder 2: 8422.0 psi
Compressive strength (to nearest 10 psi): 9170 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Partner Data Point File
Test graph for Cylinder Code 1 of 2

Source: Partner Data Point File
Test graph for Cylinder Code 2 of 2

Test was verified on 6/2/2015 ✔