Summary for Test 2020-11-18-29-4
Test performed: ASTM D624-00-re12Project Information
Project Identifiers | Project ID: 214114 DEA: 040A5394 EFIS: 0418000244 |
---|---|
DIST-CO-RTE-PM | 04-SOL-80,12-11.4/12.8, 2.1/2.8 |
Award Date | Not set |
Closeout Date | 02/24/2023 |
Work Description | Widen EB SR-12 Connector, Construct 3 ramps & 2 box girder bridges, remove existing bridge, etc. |
Location Description | I-80/I-680/Route 12 Interchange |
QA Service Level | 1 (Verified on 04/23/2019) |
Sample Information
Sample Taken Date | 11/18/2020 | Sample Unique Key | 29 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 11/30/2020 |
Sample type | Quality Assurance | A brief description of the sample | Bearing Pad |
The quantity of what the sample constitutes | 2 | From where was the sample collected | Manufacturer |
First name of sampler or witnessed by | Kayla | Last name of sampler or witnessed by | Wallace |
Title of sampler | Telephone number of sampler | ||
Laboratory sample identification | Linked DIME Sample ID | ||
The fabricator/manufacturer/facility name | Dynamic Rubber | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | SMTL TM1 - Elastomeric Bearing Pad | Mfg. Lot Number(s) | CR55-028-20 |
---|---|---|---|
Material/Compound/Elastomer ID | na | Samples Representing | 93 |
Description (size) | 1"x4"x6" | Comments | |
Description (Number of Shims) | 0 | Type of Bearing Pad | Plain |
Description (Thickness of Shims) | NA | Manufacturer(s) | Dynamic Rubber |
Batch Number | na |
Test Details
DIME Sample ID: 2020-11-18-29
DIME Test ID: 2020-11-18-29-4
Testing Lab: CT HQ - Sacramento Structural Materials Testing Laboratory
Test Method: ASTM D624-00-re12: Standard Test Method for Tear Strength of Conventional Vulcanized Rubber and Thermoplastic Elastomers
Test Release Date: 2020-12-14
Test Results
Number of specimens tested: 3
Input Type: Measured
Tester's full name: spaine
Date of test: 12/10/2020
Humidity: 50.00 %
Temperature: 72 F
Sample 1 Median Thickness: 0.077
Sample 1 Tear Strength: 276.7
Sample 2 Median Thickness: 0.085
Sample 2 Tear Strength: 307.9
Sample 3 Median Thickness: 0.08
Sample 3 Tear Strength: 267.7
UTM: 2kip
Median of the Tear Strength Values: 276.7 lb/in
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Bluehill Data Point FileTest graph for Sample 1
Source: Bluehill Data Point File
Test graph for Sample 2
Source: Bluehill Data Point File
Test graph for Sample 3
Test was verified on 12/14/2020 ✔