Summary for Test 2026-07-16-78-2

Test performed: CTM 521-June 2020

Project Information

Project IdentifiersProject ID: 1001612
DEA: 051P2104
EFIS: 0521000188
DIST-CO-RTE-PM05-MON,-1-44.3
Award Date12/19/2025
Closeout DateNot set
Work DescriptionCONSTRUCT SOLDIER PILE WALL AND STRUCTURAL CONCRETE BARRIER SLAB.
Location DescriptionMONTEREY COUNTY NEAR BIG SUR ABOUT 1.1 MILES SOUTH OF PFEIFFER CANYON BRIDGE
QA Service Level1 (Verified on 11/03/2025)

Sample Information

Sample Taken Date07/16/2026 Sample Unique Key78
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing07/17/2026
Sample typeQuality Control A brief description of the sampleType II 4x8 concrete cylinders (3)
The quantity of what the sample constitutes8.5 CY From where was the sample collectedJob Site
First name of sampler or witnessed byRyan Last name of sampler or witnessed byLegions
Title of sampler Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameGraniterock Sand City Batch Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name Bid ItemNot set

Material Information

Material TypeConcrete The concrete mix design number07S849R2
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected218267
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedBack of truck chute Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2026-07-16-78
DIME Test ID: 2026-07-16-78-2
Testing Lab: Pacific Crest Engineering, Incorporated
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2026-08-06

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Brian Apolinario
Date of test: 07/23/2026
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.01 in
Average diameter of cylinder 2: 4.00 in
Average diameter of cylinder 3: 4.01 in
Maximum load on cylinder 1: 66520 lb
Maximum load on cylinder 2: 64640 lb
Maximum load on cylinder 3: 65690 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 7 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.63 in^2
Cross sectional area of cylinder 2: 12.57 in^2
Cross sectional area of cylinder 3: 12.63 in^2
Compressive strength (to nearest 10 psi): 5200 psi
General comments (publicly viewable) (Max 1000 characters): fixing tester name

Test was verified on 8/6/2026