Sample Record
Owner Lab
- CT HQ - Sacramento Structural Materials Testing Laboratory
DIME Sample ID 2020-06-24-2
Sample is locked from editing. info
Project Information
| Project Identifiers | Project ID: 212245 DEA: 024F8604 EFIS: 0213000043 |
|---|---|
| DIST-CO-RTE-PM | 02-TRI-36-26.7/27.1 |
| Award Date | 11/02/2018 |
| Closeout Date | 05/23/2022 |
| Work Description | ROADWAY REALIGNMENT AND NEW BRIDGE CONSTRUCTION |
| Location Description | TRINITY COUNTY ABOUT 9 MILES EAST OF FOREST GLEN FROM 0.6 MILE WEST TO 0.1 MILE WEST OF ROUTE 3 |
| QA Service Level | 1 (Verified on 03/21/2017) |
Sample Information
| Sample Taken Date | 06/24/2020 | Sample Unique Key | 2 |
|---|---|---|---|
| Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 06/26/2020 |
| Sample type | Quality Assurance | A brief description of the sample | #6 x 5'-2" Dia. |
| The quantity of what the sample constitutes | 4 Samples from lot 2 | From where was the sample collected | Fabricator |
| First name of sampler or witnessed by | Osiel | Last name of sampler or witnessed by | Ramirez |
| Title of sampler | CT METS QA INSPECTOR | Telephone number of sampler | 5599740870 |
| Laboratory sample identification | Linked DIME Sample ID | ||
| The fabricator/manufacturer/facility name | TNT Rebar | Transportation Laboratory (TL) Number | |
| Inspector Lot Number from the Transportation Laboratory (TL) Form | L123-073-20 | Structure unique identifier | |
| Structure name | Bid Item | Not set |
Material Information
| Material Type | SMTL TM5 - Welded Hoops | Production or Authorization Testing | Production Testing |
|---|---|---|---|
| Service or Ultimate | Ultimate | Rebar Heat Number(s) | 1201021017 |
| Hoop Manufacturer Lot Number(s) | 2 | Material Standard Code | ASTM A706 |
| Material Grade | 60 | Rebar Size | #6 |
| Diameter of Hoop | 5'-2" | Epoxy Coated | No |
| Epoxy Coating Color | NA | Rebar Manufacturer | Nucor |
| Welding Company | TNT Rebar | Coating Standards | Uncoated |
| Weld Type | Flash Welded |
Submitted Tests
Sample File Attachments
| File Name | Extension | Date Uploaded | Actions |
|---|---|---|---|
| No results found. | |||
Test File Attachments
DIME Test ID: 2020-06-24-2-1 CTM 670-December 2013 (Verified)
DIME Test ID: 2020-06-24-2-2 CTM 670-December 2013 (Verified)
DIME Test ID: 2020-06-24-2-3 CTM 670-December 2013 (Verified)