Testing Report for 2021-07-16-19-4

Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.

Project Information

DEA: 010E7704
EFIS: 0115000009
Project ID: 214402
QA Service Level: 1
DIST-CO-RTE-PM: 01-HUM-101-R17.9/87.8
Work Description: STRENGTHEN 2 BRIDGES.
Location Description: HUMBOLDT COUNTY AT SOUTH FORK EEL RIVER AND SEPARATION AND AT ARCATA OVERHEAD
Contractor Name: Unknown
Contractor Address: Unknown
Resident Engineer: Joaquin Rodriguez
Structure Rep.: Kari Forbes

Sample Information

DIME Sample ID: 2021-07-16-19
TL Number from the TL Form: C8356670
Sample Submitted By Organization: CT QASI - Bay Area Field Laboratory
Sample Organization Contact: (707) 649-5453
Type of Sample: Quality Assurance
Type of Material: SMTL TM3 - Fastener Assembly
Sample Taken Date: 7/16/2021
Date that the sample was received by the laboratory/organization performing the testing: 7/21/2021
The quantity of what the sample constitutes: 734 assemblies total
A brief description of the sample: 1" and 5/8" A325 HDG fastener assemblies
From where was the sample collected: Fabricator
Laboratory sample identification:
Structure unique identifier:
Structure name: various
The fabricator/manufacturer/facility name: CK Johnson Industries

Material Information

Rocap Number(s): 445378AR
Heat Number(s): Bolt 100105212 Nut 80000006661 Washer 209198
Nut Mfg. Lot Number(s): 452164A
Washer Mfg. Lot Number(s): D9684
Bolt Specification: A325 Hvy Hex HDG
Bolt Length(s): 5 1/2"
Nut Specification: F563 DH HDG
Washer Specification: F436 HDG
Finish: Hot Dip Galvanized
Diameter/Size: 1" dia
Bolt Mfg. Lot Number: 445378A
Rocap Test Requirement(s): yes
Lubricant Requirements(s): yes

Test Information

DIME Test ID: 2021-07-16-19-4
Test Method: ASTM F606-14a: Standard Test Methods for Determining the Mechanical Properties of Externally and Internally Threaded Fasteners, Washers, Direct Tension Indicators, and Rivets (Proof Load with Wedge)
Date Tested: 7/21/2021
Verified Date: 7/22/2021
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Blvd,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: paul.lukkarila@dot.ca.gov
Organization Phone: (916) 227-7253
General Comments for this Test: A325
Test Result Compliance:
Additional Comments When Verified :

Submitted Test Results

Number of Bolt Samples: 1
Sample Bolt Mfg. Lot Number Size (in) Peak Load (lbf) Peak Load (kN) Wedge Angle (deg) Comments Tested By
2 445378A 1.0000 86372 384.2 10.00 A325 fsaylor
UTM: 450kip
Temperature: no data