Project Information

Project ID: 214649 DEA: 07316004 EFIS: 0715000194 QA Service Level: 1
DIST-CO-RTE-PM: 07-LA-14-60.70
Work Description: REHABILITATION FOR THE ON/OFF RAMPS AND ADJACENT SHOULDERS. UPGRADING METAL BEAM GUARDRAILS, AC DIKES, SIGN PANELS, CURB RAMPS, TRAFFIC LOOPS DETECTORS, AND SOME OTHER HIGHWAY APPURTENANCES.
Location Description: ROUTE 14 FROM PALMDALE BLVD TO KERN COUNTRY LINE.
Contractor Name: Guy F. Atkinson Construction LLC
Contractor Address: 18201 Von Karman Ave, Suite 800, Irvine, CA 92612
Resident Engineer: James Shih Structure Rep.: George Boules

Sample Information

DIME Sample ID: 2024-03-21-45
TL Number from the TL Form:
Sample Submitted By Organization: Alta Vista Solutions - Whittier
Sample Organization Contact: (510) 542-9827
Type of Sample: Quality Assurance
Type of Material: Concrete
Sample Taken Date: 03/21/2024
Date that the sample was received by the laboratory/organization performing the testing: 03/21/2024
The quantity of what the sample constitutes: 10 cubic yards
A brief description of the sample: 6x12 concrete cylinders
From where was the sample collected: Source
Laboratory sample identification: 24-0302
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: N/A

Material Information

The concrete mix design number: SCI-12622-1
The truck number from where the sample was collected:
The batch plant ticket number from where the sample was collected: 29
Concrete batch plant:
The fabricator/manufacturer designation for the sample:
A detailed description of where the material sample was collected: wheelbarrow
Where the material sample would have been placed if not sampled:
From Lot No.:
Bag Lot No.:

Test Results

Test 1 of 3

DIME Test ID: 2024-03-21-45-1
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Verified Date: 03/25/2024
Date Tested: 03/21/2024
Submitted By Organization: Alta Vista Solutions - Whittier
Organization Address: 12409 Slauson Avenue, Suite I,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90606
Organization Email: nicholas.hoffmann@oneatlas.com
Organization Phone: (510) 542-9827
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Unit system used? US Units
Number of specimens 3
Test performed With no density determined
Capped in accordance with? ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1 5.95 in
Average diameter of cylinder 2 5.96 in
Average diameter of cylinder 3 5.96 in
Cross sectional area of cylinder 1 27.81 in^2
Cross sectional area of cylinder 2 27.9 in^2
Cross sectional area of cylinder 3 27.9 in^2
Compressive strength (to nearest 10 psi) 5220 psi
Maximum load on cylinder 1 149727 lb
Maximum load on cylinder 2 141032 lb
Maximum load on cylinder 3 145531 lb
Compressive strength of cylinder 1 5383.9 psi
Type of fracture pattern of cylinder 1 2
Compressive strength of cylinder 2 5054.9 psi
Compressive strength of cylinder 3 5216.2 psi
Type of fracture pattern of cylinder 2 2
Type of fracture pattern of cylinder 3 2
Comment on any defect in either specimen or caps (Max 250 Characters) no data
Correction factor for cylinder 1 1
Correction factor for cylinder 2 1
Correction factor for cylinder 3 1
Age of specimen 42 days
Age of specimen in hours 0 hours

Test 2 of 3

DIME Test ID: 2024-03-21-45-2
Test Method: CTM 557-June 2020: Method of Test for Temperature of Freshly Mixed Hydraulic Cement Concrete
Verified Date: 03/25/2024
Date Tested: 02/08/2024
Submitted By Organization: Alta Vista Solutions - Whittier
Organization Address: 12409 Slauson Avenue, Suite I,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90606
Organization Email: nicholas.hoffmann@oneatlas.com
Organization Phone: (510) 542-9827
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Temperature 67 F

Test 3 of 3

DIME Test ID: 2024-03-21-45-3
Test Method: CTM 504-June 2010: Method of Test for Determining Air Content of Freshly Mixed Concrete by the Pressure Method
Verified Date: 03/25/2024
Date Tested: 02/08/2024
Submitted By Organization: Alta Vista Solutions - Whittier
Organization Address: 12409 Slauson Avenue, Suite I,
Organization City: Whittier
Organization State: CA
Organization Zipcode: 90606
Organization Email: nicholas.hoffmann@oneatlas.com
Organization Phone: (510) 542-9827
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Air Content 3.5 %