Sample Record for 2016-06-02-1
Note: Fields with no data or with a value of "Unknown" will not be displayed on the print out.
Project Information
Project ID: 208926 DEA: 120F96A4 EFIS: 1200020277 COOP: 120680
QA Service Level: 1
DIST-CO-RTE-PM: 12-ORA-5,96-3.0/3.7
Work Description: ADD ONE HOV LANE EACH WAY ON ROUTE 5
Location Description: SOUTH OF AVENIDA PICO TO SOUTH OF AVENIDA VISTA HERMOSA, IN ORANGE COUNTY
Contractor Name: Flatiron Western Division
Contractor Address: 27126-A Paseo Espada, Ste 1626, San Juan Capistrano, CA 92675
Resident Engineer: Behrooz Pirzadeh Structure Rep.: David Nguyen
Sample Information
DIME Sample ID: 2016-06-02-1
TL Number from the TL Form: Unknown
Sample Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Sample Organization Contact: (530) 329-6527
Type of Sample: Quality Assurance
Type of Material: SMTL TM5 - Couplers
Sample Taken Date: 06/02/2016
Date that the sample was received by the laboratory/organization performing the testing: 06/03/2016
The quantity of what the sample constitutes: 4
A brief description of the sample: Barsplice Griptwist coupler
From where was the sample collected: Job Site
Laboratory sample identification: Unknown
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Integrity Rebar
Material Information
Production or Authorization Testing: Production Testing
Service or Ultimate: Service
Material Standard Code: ASTM A706
Material Grade: 60
Rebar Manufacturer: Gerdau
Coupler Manufacturer: Barsplice
Intermediate Assembler or Fabricator: Unknown
Rebar Size: #8
Coupler Model: GripTwist
Coating Standards: Uncoated
Shape of Rebar: Straight
Rebar Hoop Diameter: Unknown
Rebar Hoop Fabricator: Unknown
Coupler Component Heat/Lot Number(s): A152824, A152547, A153834, A153597
Rebar Heat Number(s): 65021930
Rebar Size 2 : NA
Coupler Unique ID:
Test Results
Test 1 of 3
DIME Test ID: 2016-06-02-1-1
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 06/08/2016
Date Tested: 06/03/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance: complies
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Slip (inch) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 1 | 0 | #8/25mm | 0.79 | -0.001 | 71772 | 90851 | Service Splice | Brian |
| |
Temperature
|
72 F
|
UTM
|
400KIP
|
Halo ID
|
Small
|
Test 2 of 3
DIME Test ID: 2016-06-02-1-2
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 06/08/2016
Date Tested: 06/03/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance: complies
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Slip (inch) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 2 | 0 | #8/25mm | 0.79 | 0 | 74492 | 94294 | Service Splice | Brian |
| |
Temperature
|
72 F
|
UTM
|
400KIP
|
Halo ID
|
Small
|
Test 3 of 3
DIME Test ID: 2016-06-02-1-3
Test Method: CTM 670-December 2013: Method of Tests for Mechanical and Welded Reinforcing Steel Splices (Tensile Slip)
Verified Date: 06/08/2016
Date Tested: 06/03/2016
Submitted By Organization: CT HQ - Sacramento Structural Materials Testing Laboratory
Organization Address: 5900 Folsom Boulevard,
Organization City: Sacramento
Organization State: CA
Organization Zipcode: 95819
Organization Email: joshua.moore@dot.ca.gov
Organization Phone: (530) 329-6527
General Comments for this Test: Service Splice
Test Result Compliance: complies
Additional Comments When Verified:
Number of Samples
|
1
|
Sample | Mfg. Lot Number(s) | Size | Area (sqin) | Slip (inch) | Peak Load (lbf) | Peak Stress (psi) | Comments | Tested By | 3 | 0 | #8/25mm | 0.79 | 0 | 75101 | 95065 | Service Splice | Brian |
| |
Temperature
|
72 F
|
UTM
|
400KIP
|
Halo ID
|
Small
|