Project ID: 213469 DEA: 024C40V4 EFIS: 0218000125
QA Service Level: 1
DIST-CO-RTE-PM: 02-SHA-5-R3.8/R11.7
Work Description: WIDEN TO 6 LANES, BRIDGE REPLACEMENT AND WIDENING AND ROADWAY REHAB
Location Description: SHASTA COUNTY IN AND NEAR ANDERSON FROM ROUTE 5/273 SEPARATION TO 0.4 MILE SOUTH OF CHURN CREEK ROAD OVERCROSSING
Contractor Name: J.F. SHEA CONSTRUCTION
Contractor Address: P.O. BOX 494519, REDDING, CA 96049-4519
Resident Engineer: Henry Benner Structure Rep.: Eric Chaffee
DIME Sample ID: 2019-07-30-17
TL Number from the TL Form: 736160
Sample Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Sample Organization Contact: (530) 225-3194
Type of Sample: Verification
Type of Material: Hot Mix Asphalt
Sample Taken Date: 07/30/2019
Date that the sample was received by the laboratory/organization performing the testing: 07/30/2019
The quantity of what the sample constitutes: JMF Verification
A brief description of the sample: 1/2-inch Type A HMA (PG 64-10), 15% RAP, 1.0% Lime
From where was the sample collected: Manufacturer
Laboratory sample identification: D78054
Structure unique identifier:
Structure name:
The fabricator/manufacturer/facility name: Fawndale Rock and Asphalt - Redding, CA
DIME Test ID: 2019-07-30-17-1
Test Method: AASHTO T308-10: Standard Method of Test for Determining the Asphalt Binder Content of Hot Mix Asphalt (HMA) by the Ignition Method (Method A) (Asphalt Binder Content)
Verified Date: 03/10/2020
Date Tested: 08/20/2019
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test:
Test Result Compliance: not applicable
Additional Comments When Verified:
What temperature unit is used?
|
Fahrenheit
|
Test procedure used?
|
Method A
|
Mass of HMA Sample prior to ignition
|
1608.6 g
|
Corrected Asphalt Binder Content
|
5.15 %
|
Mass Loss
|
no data
|
Correction Factor (Percent by mass of HMA Specimen)
|
0.29 %
|
Moisture Content
|
0.00 %
|
Temperature Compensation Factor
|
no data
|
Test Temperature
|
1000 F
|
DIME Test ID: 2019-07-30-17-2
Test Method: AASHTO T209-12: Standard Method of Test for Theoretical Maximum Specific Gravity (Gmm) and Density of Asphalt Mixtures (Maximum Specific Gravity)
Verified Date: 03/10/2020
Date Tested: 08/16/2019
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Number of tests
|
1
|
What is the unit of measurement for theoretical density?
|
US Units
|
Mass Determination
|
Air
|
Specific Gravity for Sample 1
|
2.524
|
Theoretical maximum density at 25°C (77°F)
|
no data
|
DIME Test ID: 2019-07-30-17-3
Test Method: AASHTO T275-07r12: Standard Method of Test for Bulk Specific Gravity (Gmb) of Compacted Asphalt Mixtures Using Paraffin-Coated Specimens (Bulk Specific Gravity)
Verified Date: 03/10/2020
Date Tested: 08/01/2019
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test:
Test Result Compliance:
Additional Comments When Verified:
Bulk Specific Gravity
|
2.392
|
Bulk Specific Gravity 2
|
2.390
|
Bulk Specific Gravity 3
|
2.390
|
Average Bulk Specific Gravity
|
2.391
|
DIME Test ID: 2019-07-30-17-4
Test Method: AASHTO T269-14: Standard Method of Test for Percent Air Voids in Compacted Dense and Open Asphalt Mixtures (Air Void)
Verified Date: 03/10/2020
Date Tested: 08/01/2019
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Percent Air Voids
|
5.2 %
|
Percent Air Voids 2
|
5.3
|
Percent Air Voids 3
|
5.3
|
Percent Air Voids Average
|
5.3
|
DIME Test ID: 2019-07-30-17-5
Test Method: AASHTO T283-14: Standard Method of Test for Resistance of Compacted Asphalt Mixtures to Moisture-Induced Damage (Moisture Content)
Verified Date: 03/10/2020
Date Tested: 08/05/2019
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Unit system used?
|
SI Units
|
Average Dry Tensile Strength
|
146 psi
|
Average Wet Tensile Strength
|
130 psi
|
Tensile Strength Ratio
|
89
|
DIME Test ID: 2019-07-30-17-6
Test Method: AASHTO T324-14: Standard Method of Test for Hamburg Wheel-Track Testing of Compacted Asphalt Mixtures (Hamburg Wheel Track)
Verified Date: 03/10/2020
Date Tested: 08/02/2019
Submitted By Organization: CT D02 - Redding Northern Regional Laboratory
Organization Address: 1657 Riverside Drive,
Organization City: Redding
Organization State: CA
Organization Zipcode: 96001
Organization Email: ward.jenkins@dot.ca.gov
Organization Phone: 530-225-3194
General Comments for this Test:
Test Result Compliance: complies
Additional Comments When Verified:
Specified minimum number of passes at ½” rut depth, or number of passes at ½” rut depth if applicable (Wheel A)
|
25000
|
Specified minimum number of passes at ½” rut depth, or number of passes at ½” rut depth if applicable (Wheel B)
|
25000
|
Impression at specified number of passes, or specified maximum impression if applicable (Wheel A)
|
2.8 mm
|
Impression at specified number of passes, or specified maximum impression if applicable (Wheel B)
|
2.5 mm
|
Stripping Inflection Point (Wheel A)
|
>25000
|
Stripping Inflection Point (Wheel B)
|
>25000
|