Summary for Test 2020-07-06-11-1
Test performed: ASTM C39-17aProject Information
Project Identifiers | Project ID: 212112 DEA: 080C2514 EFIS: 0816000076 COOP: 081645 |
---|---|
DIST-CO-RTE-PM | 08-SBD-10-0.0/13.2 |
Award Date | 06/06/2018 |
Closeout Date | Not set |
Work Description | Design-Build of I-10 Corridor Contract 1 - Adding 2 new Express Lanes |
Location Description | LA/SBD County Line to PM 13.2 near I-15 |
QA Service Level | 1 (Verified on 10/16/2019) |
Sample Information
Sample Taken Date | 07/06/2020 | Sample Unique Key | 11 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 07/09/2020 |
Sample type | Quality Assurance | A brief description of the sample | 6x12 concrete cylinders |
The quantity of what the sample constitutes | 4 | From where was the sample collected | Fabricator |
First name of sampler or witnessed by | David | Last name of sampler or witnessed by | Grey |
Title of sampler | QA Inspector | Telephone number of sampler | |
Laboratory sample identification | Linked DIME Sample ID | ||
The fabricator/manufacturer/facility name | Confab Shafter | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | 54-0444 | |
Structure name | Sultana Bridge OC |
Material Information
Material Type | Concrete | The concrete mix design number | SCC-S9_8-10F |
---|---|---|---|
The truck number from where the sample was collected | Unknown | The batch plant ticket number from where the sample was collected | 2172 |
Concrete batch plant | Unknown | The fabricator/manufacturer designation for the sample | Unknown |
A detailed description of where the material sample was collected | tailgate | Where the material sample would have been placed if not sampled | Unknown |
From Lot No. | Unknown | Bag Lot No. | Unknown |
Test Details
DIME Sample ID: 2020-07-06-11
DIME Test ID: 2020-07-06-11-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2020-08-04
Test Results
Unit system used?: US Units
Number of specimens: 4
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 08/03/2020
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.01 in
Average diameter of cylinder 3: 6.01 in
Average diameter of cylinder 4: 6.00 in
Maximum load on cylinder 1: 273120 lb
Maximum load on cylinder 2: 264725 lb
Maximum load on cylinder 3: 264360 lb
Maximum load on cylinder 4: 268970 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 2
Type of fracture pattern of cylinder 4: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Correction factor for cylinder 3: 1
Correction factor for cylinder 4: 1
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Cross sectional area of cylinder 3: 28.37 in^2
Cross sectional area of cylinder 4: 28.27 in^2
Compressive strength of cylinder 1: 9627.1 psi
Compressive strength of cylinder 2: 9331.2 psi
Compressive strength of cylinder 3: 9318.3 psi
Compressive strength of cylinder 4: 9514.3 psi
Compressive strength (to nearest 10 psi): 9450 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 8/4/2020 ✔