Summary for Test 2014-09-26-1-2
Test performed: ASTM C39-10Project Information
Project Identifiers | Project ID: 7285 DEA: 040120T4 EFIS: 0400000027 |
---|---|
DIST-CO-RTE-PM | 04-SF-80-12.6/13.9 |
Award Date | 11/27/2012 |
Closeout Date | Not set |
Work Description | CONSTRUCT BRIDGE, ROADWAYS, ELECTRICAL, BUILDINGS AND REMOVE BRIDGES |
Location Description | THE CITY AND COUNTY OF SAN FRANCISCO FROM THE YERBA BUENA TUNNEL TO 1.3 KM EAST OF THE YERBA BUENA TUNNEL |
QA Service Level | 1 (Verified on 10/29/2012) |
Sample Information
Sample Taken Date | 09/26/2014 | Sample Unique Key | 1 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | No | Date that the sample was received by the laboratory/organization performing the testing | 10/03/2014 |
Sample type | Department Acceptance | A brief description of the sample | concrete cylinders |
The quantity of what the sample constitutes | Acceptance test 2 at 7 days 2 at 24 days | From where was the sample collected | Other |
First name of sampler or witnessed by | Mohan | Last name of sampler or witnessed by | Ayadurai |
Title of sampler | Transportation Engineer | Telephone number of sampler | 707-694-4751 |
Laboratory sample identification | Linked DIME Sample ID | Not set | |
The fabricator/manufacturer/facility name | Central Concrete | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | 42S Column | |
Structure name | West Tie In Edge Beam |
Material Information
Material Type | Concrete | The concrete mix design number | D101C5E |
---|---|---|---|
The truck number from where the sample was collected | 1686 | The batch plant ticket number from where the sample was collected | 18901444 |
Concrete batch plant | 12 | The fabricator/manufacturer designation for the sample | MCM Construction |
A detailed description of where the material sample was collected | Job site | Where the material sample would have been placed if not sampled | Not set |
From Lot No. | Not set | Bag Lot No. | Not set |
Test Details
DIME Sample ID: 2014-09-26-1
DIME Test ID: 2014-09-26-1-2
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-10-20
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Steve Wake
Date of test: 10/20/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 5.98 in
Maximum load on cylinder 1: 132289 lb
Maximum load on cylinder 2: 129087 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 24 days
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.09 in^2
Compressive strength of cylinder 1: 4679.5 psi
Compressive strength of cylinder 2: 4595.5 psi
Compressive strength (to nearest 10 psi): 4640 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 10/20/2014 ✔