Summary for Test 2024-09-30-84-1
Test performed: CTM 521-June 2020Project Information
Project Identifiers | Project ID: 994443 DEA: 053307C4 EFIS: 0514000028 |
---|---|
DIST-CO-RTE-PM | 05-SLO-41,46-44.5/45.3,54.0/57.8 |
Award Date | 02/27/2023 |
Closeout Date | Not set |
Work Description | Wye Segment - Route 41/46 Separation |
Location Description | Not set |
QA Service Level | 1 (Verified on 12/16/2022) |
Sample Information
Sample Taken Date | 09/30/2024 | Sample Unique Key | 84 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 10/01/2024 |
Sample type | Acceptance | A brief description of the sample | 4x8 cylinders |
The quantity of what the sample constitutes | CCB OF Abut 2L Ex. WW- 3T36H000 | From where was the sample collected | Manufacturer |
First name of sampler or witnessed by | Sal | Last name of sampler or witnessed by | Zepeda |
Title of sampler | Tester | Telephone number of sampler | |
Laboratory sample identification | Linked DIME Sample ID | ||
The fabricator/manufacturer/facility name | Holliday Rock Paso Robles | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name | Cholame Creek Bridge Overflow Abut 2L & Ext. WW |
Material Information
Material Type | Concrete | The concrete mix design number | 3T36H000 |
---|---|---|---|
The truck number from where the sample was collected | The batch plant ticket number from where the sample was collected | NA | |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | Mix Truck | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2024-09-30-84
DIME Test ID: 2024-09-30-84-1
Testing Lab: CT D05 - Whitley Gardens Field Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2024-10-29
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Kyle Engen
Date of test: 10/28/2024
Capped in accordance with?: ASTM C1231 - Unbonded Elastomeric Pad Cap
Average diameter of cylinder 1: 4.02 in
Average diameter of cylinder 2: 4.01 in
Average diameter of cylinder 3: 4.01 in
Maximum load on cylinder 1: 73386 lb
Maximum load on cylinder 2: 75320 lb
Maximum load on cylinder 3: 75164 lb
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 4
Type of fracture pattern of cylinder 3: 4
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 12.69 in^2
Cross sectional area of cylinder 2: 12.63 in^2
Cross sectional area of cylinder 3: 12.63 in^2
Compressive strength of cylinder 1: 5,783.0 psi
Compressive strength of cylinder 2: 5,963.6 psi
Compressive strength of cylinder 3: 5,951.2 psi
Compressive strength (to nearest 10 psi): 5900 psi
General comments (publicly viewable) (Max 1000 characters):
Test File Attachments
File Name | Extension | File Size | Date Uploaded | Test ID | Actions |
---|---|---|---|---|---|
05-3307C4_370095_240930_KEE_CTM 521_CCB OF Abut 2L-Ext WW_28 Day_3x_1 | 117.40 KB | 10/29/2024 | 2024-09-30-84-1 | Info |
Test was verified on 10/29/2024 ✔