Summary for Test 2024-01-18-13-1
Test performed: ASTM C39-10Project Information
Project Identifiers | Project ID: 993815 DEA: 081C0814 EFIS: 0816000086 |
---|---|
DIST-CO-RTE-PM | 08-RIV-10-R60.7/R74.3 |
Award Date | 03/28/2022 |
Closeout Date | Not set |
Work Description | I-10 PAVEMENT REHABILITATION (SEGMENT 1) PROJECT |
Location Description | Coachella |
QA Service Level | 1 (Verified on 05/03/2022) |
Sample Information
Sample Taken Date | 01/18/2024 | Sample Unique Key | 13 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 01/19/2024 |
Sample type | Quality Assurance | A brief description of the sample | Concrete Cylinders |
The quantity of what the sample constitutes | 3 | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Mohammad | Last name of sampler or witnessed by | Maswadi |
Title of sampler | ASR | Telephone number of sampler | |
Laboratory sample identification | 1051-72 | Linked DIME Sample ID | |
The fabricator/manufacturer/facility name | NA | Transportation Laboratory (TL) Number | 1051-72 |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | CT675F25D |
---|---|---|---|
The truck number from where the sample was collected | 284 | The batch plant ticket number from where the sample was collected | 913976 |
Concrete batch plant | NA | The fabricator/manufacturer designation for the sample | |
A detailed description of where the material sample was collected | BROWN ARROYO BRIDGE | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2024-01-18-13
DIME Test ID: 2024-01-18-13-1
Testing Lab: CT D08 - Fontana Southern Regional Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2024-02-20
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: Matthew Clayton
Date of test: 02/15/2024
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 4.02 in
Average diameter of cylinder 2: 4.02 in
Average diameter of cylinder 3: 4.02 in
Maximum load on cylinder 1: 91060 lb
Maximum load on cylinder 2: 93540 lb
Maximum load on cylinder 3: 89180 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Type of fracture pattern of cylinder 3: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1.00
Correction factor for cylinder 2: 1.00
Correction factor for cylinder 3: 1.00
Age of specimen: 28 days
Cross sectional area of cylinder 1: 12.69 in^2
Cross sectional area of cylinder 2: 12.69 in^2
Cross sectional area of cylinder 3: 12.69 in^2
Compressive strength of cylinder 1: 7,175.7 psi
Compressive strength of cylinder 2: 7,371.2 psi
Compressive strength of cylinder 3: 7,027.6 psi
Compressive strength (to nearest 10 psi): 7190 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 2/20/2024 ✔