Summary for Test 2022-09-08-3-1
Test performed: CTM 521-June 2020
Warning: The test results shown on this page have been superseded and are invalid.
This information is for reference only.
Please click this
link
to view the corrected test.
Project Information
Project Identifiers | Project ID: 993150 DEA: 051G9704 EFIS: 0516000008 |
---|---|
DIST-CO-RTE-PM | 05-SB-135-11.7/17.8 |
Award Date | 09/27/2021 |
Closeout Date | 03/28/2023 |
Work Description | COLD PLANE, OVERLAY ROADWAY WITH RHMA (GAP GRADED) AND ADA CURB RAMPS. |
Location Description | SANTA BARBARA COUNTY IN AND NEAR SANTA MARIA FROM LAKEVIEW ROAD TO NORTH SANTA MARIA CONNECTOR |
QA Service Level | 1 (Verified on 08/09/2021) |
Sample Information
Sample Taken Date | 09/08/2022 | Sample Unique Key | 3 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 09/08/2022 |
Sample type | Quality Assurance | A brief description of the sample | Class 2 Concrete |
The quantity of what the sample constitutes | 10.5 Cy | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Isaac | Last name of sampler or witnessed by | Gleffe |
Title of sampler | ARET | Telephone number of sampler | 18053191237 |
Laboratory sample identification | Linked DIME Sample ID | ||
The fabricator/manufacturer/facility name | Calportland/Donaven | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | 590GN1010 |
---|---|---|---|
The truck number from where the sample was collected | load 1 | The batch plant ticket number from where the sample was collected | 1735273 |
Concrete batch plant | The fabricator/manufacturer designation for the sample | ||
A detailed description of where the material sample was collected | Dischard fron concrete truck into wheelbarrow. | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2022-09-08-3
DIME Test ID: 2022-09-08-3-1
Testing Lab: CT D05 - Santa Maria Field Laboratory
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2022-09-22
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Salvador Lopez-Zamora
Date of test: 09/08/2022
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.00 in
Maximum load on cylinder 1: 109803 lb
Maximum load on cylinder 2: 118959 lb
Type of fracture pattern of cylinder 1: 5
Type of fracture pattern of cylinder 2: 5
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 28 days
Age of specimen in hours: 678 hours
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength of cylinder 1: 3870.4 psi
Compressive strength of cylinder 2: 4208.0 psi
Compressive strength (to nearest 10 psi): 4040 psi
General comments (publicly viewable) (Max 1000 characters): Complies
Test was verified on 9/22/2022 ✔