Summary for Test 2022-04-12-25-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 215396
DEA: 042K8404
EFIS: 0417000031
DIST-CO-RTE-PM04-SOL-29,80-0.0,0.8/1.6
Award Date03/26/2021
Closeout Date02/16/2024
Work DescriptionHMA, STRUCTURAL CONCRETE, CIDH PILING AND REBAR.
Location DescriptionSOLANO COUNTY IN VALLEJO AT ROUTE 80/29 SEPARATION AND ON ROUTE 80 FROM 0.2 MILE NORTH OF CARQUINEZ BRIDGE TOLL PLAZA TO 0.3 MILE SOUTH OF MAGAZINE STREET OVERCROSSING
QA Service Level1 (Verified on 01/25/2021)

Sample Information

Sample Taken Date04/12/2022 Sample Unique Key25
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing04/20/2022
Sample typeQuality Assurance A brief description of the sample4x8 concrete cylinders
The quantity of what the sample constitutes3 cylinders From where was the sample collectedJob Site
First name of sampler or witnessed byNoel Last name of sampler or witnessed byAquino
Title of samplerRE Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameUnknown Transportation Laboratory (TL) Number211019
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design number1613820
The truck number from where the sample was collected The batch plant ticket number from where the sample was collectedUnknown
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedChute Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2022-04-12-25
DIME Test ID: 2022-04-12-25-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2022-05-10

Test Results


Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: SA
Date of test: 05/10/2022
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 4.01 in
Average diameter of cylinder 2: 4.02 in
Average diameter of cylinder 3: 4.02 in
Maximum load on cylinder 1: 108808 lbf
Maximum load on cylinder 2: 109728 lbf
Maximum load on cylinder 3: 109797 lbf
Type of fracture pattern of cylinder 1: 4
Type of fracture pattern of cylinder 2: 3
Type of fracture pattern of cylinder 3: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Correction factor for cylinder 3: 1
Age of specimen: 28 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.63 in^2
Cross sectional area of cylinder 2: 12.69 in^2
Cross sectional area of cylinder 3: 12.69 in^2
Compressive strength of cylinder 1: 8616.0 psi
Compressive strength of cylinder 2: 8645.0 psi
Compressive strength of cylinder 3: 8651 psi
Compressive strength (to nearest 10 psi): 8640 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Bluehill Data Point File
Test graph for Cylinder Code 1 of 3

Source: Bluehill Data Point File
Test graph for Cylinder Code 2 of 3

Source: Bluehill Data Point File
Test graph for Cylinder Code 3 of 3

Test was verified on 5/10/2022