Summary for Test 2021-04-21-36-1
Test performed: ASTM C39-18Project Information
Project Identifiers | Project ID: 214909 DEA: 120N8604 EFIS: 1214000123 |
---|---|
DIST-CO-RTE-PM | 12-ORA-73-23.7/24.1 |
Award Date | 06/25/2020 |
Closeout Date | 01/09/2023 |
Work Description | REPLACE STRUCTURAL CONCRETE BRIDGE & RETAINING WALL; & PLACE HMA. |
Location Description | ORANGE COUNTY IN NEWPORT BEACH FROM 0.3 MILE NORTH OF BISON AVENUE TO 0.3 MILE SOUTH OF UNIVERSITY DRIVE |
QA Service Level | 1 (Verified on 07/21/2020) |
Sample Information
Sample Taken Date | 04/21/2021 | Sample Unique Key | 36 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 04/22/2021 |
Sample type | Quality Control | A brief description of the sample | CIP Concrete |
The quantity of what the sample constitutes | Below 1st 100 CY | From where was the sample collected | Job Site |
First name of sampler or witnessed by | ALAN | Last name of sampler or witnessed by | WHITCOMB |
Title of sampler | Telephone number of sampler | 7149746316 | |
Laboratory sample identification | C042121-102 | Linked DIME Sample ID | |
The fabricator/manufacturer/facility name | Cemex | Transportation Laboratory (TL) Number | |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name | Bent 2 Cap |
Material Information
Material Type | Concrete | The concrete mix design number | 1614705 |
---|---|---|---|
The truck number from where the sample was collected | 10070515 | The batch plant ticket number from where the sample was collected | 29593722 |
Concrete batch plant | Irvine | The fabricator/manufacturer designation for the sample | 1614705 |
A detailed description of where the material sample was collected | Jobsite | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2021-04-21-36
DIME Test ID: 2021-04-21-36-1
Testing Lab: Sequoia Consultants
Test Method: ASTM C39-18: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2022-02-18
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Calculated
Tester's full name: Clayton Morris
Date of test: 05/19/2021
Average diameter of cylinder 1: 6.00 in
Average diameter of cylinder 2: 6.00 in
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Maximum load on cylinder 1: 177560 lb
Maximum load on cylinder 2: 172700 lb
Type of fracture pattern of cylinder 1: 3
Type of fracture pattern of cylinder 2: 3
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.27 in^2
Cross sectional area of cylinder 2: 28.27 in^2
Compressive strength (to nearest 10 psi): 6200 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 2/18/2022 ✔