Summary for Test 2022-01-20-59-1
Test performed: CTM 521-June 2020Project Information
Project Identifiers | Project ID: 215164 DEA: 07317304 EFIS: 0715000237 |
---|---|
DIST-CO-RTE-PM | 07-LA-60-0.0/R3.2,11.8/R21.5 |
Award Date | Not set |
Closeout Date | 08/01/2023 |
Work Description | UPGRADE EXISTING OVERHEAD AND ROADSIDE SIGN PANELS. |
Location Description | LOS ANGELS COUNTY FROM 0.4 MILE WEST OF ROUTE 5/60 SEPARATION TO ROUTE 60/710 SEPARATION AND FROM ROUTE 60/605 SEPARATION TO FAIRWAY DRIVE UNDERCROSSING |
QA Service Level | 1 (Verified on 02/18/2021) |
Sample Information
Sample Taken Date | 01/20/2022 | Sample Unique Key | 59 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 01/24/2022 |
Sample type | Acceptance | A brief description of the sample | PCC cylinders CIDH Piles |
The quantity of what the sample constitutes | 130 CY | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Rick | Last name of sampler or witnessed by | Jensen |
Title of sampler | Assistant Structure Representative | Telephone number of sampler | |
Laboratory sample identification | 22-0019 | Linked DIME Sample ID | |
The fabricator/manufacturer/facility name | Associated | Transportation Laboratory (TL) Number | 21082502 |
Inspector Lot Number from the Transportation Laboratory (TL) Form | Structure unique identifier | ||
Structure name |
Material Information
Material Type | Concrete | The concrete mix design number | SL590330 |
---|---|---|---|
The truck number from where the sample was collected | LOAD 1 | The batch plant ticket number from where the sample was collected | 6799092 |
Concrete batch plant | Associated | The fabricator/manufacturer designation for the sample | |
A detailed description of where the material sample was collected | Chute | Where the material sample would have been placed if not sampled | |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2022-01-20-59
DIME Test ID: 2022-01-20-59-1
Testing Lab: CT D07 - Materials Field Laboratory, Unit 1953
Test Method: CTM 521-June 2020: Method of Test for Compressive Strength of Molded Concrete Cylinders
Test Release Date: 2022-02-17
Test Results
Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Arnold Truong
Date of test: 02/17/2022
Capped in accordance with?: ASTM C617 - Sulfur Mortar Cap
Average diameter of cylinder 1: 6.01 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 149655 lb
Maximum load on cylinder 2: 149788 lb
Type of fracture pattern of cylinder 1: 2
Type of fracture pattern of cylinder 2: 2
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 28 days
Age of specimen in hours: 0 hours
Cross sectional area of cylinder 1: 28.37 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 5275.1 psi
Compressive strength of cylinder 2: 5279.8 psi
Compressive strength (to nearest 10 psi): 5280 psi
General comments (publicly viewable) (Max 1000 characters):
Test was verified on 2/17/2022 ✔