Summary for Test 2021-08-09-5-1
Test performed: ASTM C39-17aProject Information
Project Identifiers | Project ID: 214562 DEA: 040J7104 EFIS: 0414000029 |
---|---|
DIST-CO-RTE-PM | 04-SOL-80-1.8/4.4 |
Award Date | 03/17/2020 |
Closeout Date | 02/29/2024 |
Work Description | RAISE BRIDGE AND PLACE STRUCTURAL CONCRETE. |
Location Description | SOLANO COUNTY IN VALLEJO AT VARIOUS LOCATIONS |
QA Service Level | 1 (Verified on 12/03/2019) |
Sample Information
Sample Taken Date | 08/09/2021 | Sample Unique Key | 5 |
---|---|---|---|
Will the laboratory/organization for which you are a member perform testing on this material sample? | Yes | Date that the sample was received by the laboratory/organization performing the testing | 08/10/2021 |
Sample type | Quality Assurance | A brief description of the sample | Magazine Approach Abut 5 |
The quantity of what the sample constitutes | 3 Cylinders | From where was the sample collected | Job Site |
First name of sampler or witnessed by | Brandon | Last name of sampler or witnessed by | Biando |
Title of sampler | TE Civil | Telephone number of sampler | 510-867-6121 |
Laboratory sample identification | 28 | Linked DIME Sample ID | NA |
The fabricator/manufacturer/facility name | Syar Lake Herman | Transportation Laboratory (TL) Number | TL-502 |
Inspector Lot Number from the Transportation Laboratory (TL) Form | NA | Structure unique identifier | 23-0066 |
Structure name | Magazine Street OC |
Material Information
Material Type | Concrete | The concrete mix design number | CT072AC5 |
---|---|---|---|
The truck number from where the sample was collected | 8096 | The batch plant ticket number from where the sample was collected | 81143622 |
Concrete batch plant | Syar Industries Lake Herman | The fabricator/manufacturer designation for the sample | |
A detailed description of where the material sample was collected | wheelbarrow | Where the material sample would have been placed if not sampled | Jobsite Sidewalk |
From Lot No. | Bag Lot No. |
Test Details
DIME Sample ID: 2021-08-09-5
DIME Test ID: 2021-08-09-5-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2021-08-16
Test Results
Unit system used?: US Units
Number of specimens: 3
Test performed: With no density determined
Input Type: Measured
Tester's full name: SA
Date of test: 08/16/2021
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 4.03 in
Average diameter of cylinder 2: 4.03 in
Average diameter of cylinder 3: 4.04 in
Maximum load on cylinder 1: 65836 lbf
Maximum load on cylinder 2: 62501 lbf
Maximum load on cylinder 3: 64470 lbf
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Type of fracture pattern of cylinder 3: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Correction factor for cylinder 3: 1
Age of specimen: 7 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 12.76 in^2
Cross sectional area of cylinder 2: 12.76 in^2
Cross sectional area of cylinder 3: 12.82 in^2
Compressive strength of cylinder 1: 5161.0 psi
Compressive strength of cylinder 2: 4900.0 psi
Compressive strength of cylinder 3: 5029 psi
Compressive strength (to nearest 10 psi): 5030 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Bluehill Data Point FileTest graph for Cylinder Code 1 of 3
Source: Bluehill Data Point File
Test graph for Cylinder Code 2 of 3
Source: Bluehill Data Point File
Test graph for Cylinder Code 3 of 3
Test was verified on 8/16/2021 ✔