Summary for Test 2015-03-03-1-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 7463
DEA: 042640U4
EFIS: 0412000195
DIST-CO-RTE-PM04-SON-101-0.9/3.6
Award Date11/02/2012
Closeout Date06/03/2020
Work DescriptionCONSTRUCT PETALUMA BLVD SOUTH INTERCHANGE, REPLACE PETALUMA RIVER BR
Location DescriptionSONOMA COUNTY IN AND NEAR PETALUMA FROM GUNN DRIVE TO ROUTE 101/116 SEPARATION AND OVERHEAD
QA Service Level1 (Verified on 09/11/2012)

Sample Information

Sample Taken Date03/03/2015 Sample Unique Key1
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing03/06/2015
Sample typeVerification A brief description of the sampleconcrete cylinders
The quantity of what the sample constitutesUnknown From where was the sample collectedJob Site
First name of sampler or witnessed byPhil Last name of sampler or witnessed byLatasa
Title of samplerUnknown Telephone number of samplerUnknown
Laboratory sample identificationUnknown Linked DIME Sample IDUnknown
The fabricator/manufacturer/facility nameOn site Transportation Laboratory (TL) Number203430
Inspector Lot Number from the Transportation Laboratory (TL) Form203430 Structure unique identifierUnknown
Structure nameUnknown

Material Information

Material TypeConcrete The concrete mix design numberUnknown
The truck number from where the sample was collectedUnknown The batch plant ticket number from where the sample was collectedunknown
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedfrom mix truck Where the material sample would have been placed if not sampledNot set
From Lot No.Not set Bag Lot No.Not set

Test Details

DIME Sample ID: 2015-03-03-1
DIME Test ID: 2015-03-03-1-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2015-04-01

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Bang
Date of test: 04/01/2015
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 155116 lb
Maximum load on cylinder 2: 163282 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 29 days
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 5450.3 psi
Compressive strength of cylinder 2: 5755.4 psi
Compressive strength (to nearest 10 psi): 5600 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Partner Data Point File
Test graph for Cylinder Code 1 of 2

Source: Partner Data Point File
Test graph for Cylinder Code 2 of 2

Test was verified on 4/1/2015