Summary for Test 2020-09-04-4-1

Test performed: ASTM C39-17a

Project Information

Project IdentifiersProject ID: 212914
DEA: 031E0604
EFIS: 0312000068
DIST-CO-RTE-PM03-YUB-70-15.5/16.5
Award Date07/31/2019
Closeout Date08/30/2023
Work DescriptionSIMMERLY SLOUGH BRIDGE REPLACEMENT BR 16-0019 WITH BR 16-0055.
Location DescriptionNEAR MARYSVILLE, FROM 0.1 MILE NORTH OF BINNEY JUNCTION UNDERPASS TO 0.3 MILE NORTH OF LAURELLEN ROAD, AT SIMMERLY SLOUGH BRIDGE BR 16-0019.
QA Service Level1 (Verified on 08/22/2019)

Sample Information

Sample Taken Date09/04/2020 Sample Unique Key4
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing09/08/2020
Sample typeQuality Assurance A brief description of the sample6x12 concrete cylinders
The quantity of what the sample constitutes2 cylinders From where was the sample collectedJob Site
First name of sampler or witnessed byTravis Last name of sampler or witnessed byChristie
Title of sampler Telephone number of sampler
Laboratory sample identification Linked DIME Sample ID
The fabricator/manufacturer/facility nameJobsite Transportation Laboratory (TL) Number80-SS3-01
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifier
Structure name

Material Information

Material TypeConcrete The concrete mix design number1613514
The truck number from where the sample was collected The batch plant ticket number from where the sample was collected00000000000000000
Concrete batch plant The fabricator/manufacturer designation for the sample
A detailed description of where the material sample was collectedJobsite Where the material sample would have been placed if not sampled
From Lot No. Bag Lot No.

Test Details

DIME Sample ID: 2020-09-04-4
DIME Test ID: 2020-09-04-4-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-17a: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2020-09-11

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: PM
Date of test: 09/11/2020
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 5.98 in
Average diameter of cylinder 2: 5.95 in
Maximum load on cylinder 1: 127918 lbf
Maximum load on cylinder 2: 129039 lbf
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: 1
Age of specimen: 7 days
Age of specimen in hours: no data
Cross sectional area of cylinder 1: 28.09 in^2
Cross sectional area of cylinder 2: 27.81 in^2
Compressive strength of cylinder 1: 4554.0 psi
Compressive strength of cylinder 2: 4641.0 psi
Compressive strength (to nearest 10 psi): 4600 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Bluehill Data Point File
Test graph for Cylinder Code 1 of 2

Source: Bluehill Data Point File
Test graph for Cylinder Code 2 of 2

Test was verified on 9/11/2020