Test 2014-10-21-1-1 (ASTM C39-10) Summary

Project Information
Project IdentifiersProject ID: 7463
DEA: 042640U4
EFIS: 0412000195
DIST-CO-RTE-PM04-SON-101-0.9/3.6
Work DescriptionCONSTRUCT PETALUMA BLVD SOUTH INTERCHANGE, REPLACE PETALUMA RIVER BR
Location DescriptionSONOMA COUNTY IN AND NEAR PETALUMA FROM GUNN DRIVE TO ROUTE 101/116 SEPARATION AND OVERHEAD
Sample Information
Sample Taken Date10/21/2014 Sample Unique Key1
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing11/7/2014
Sample typeQuality Control A brief description of the samplecylinders
The quantity of what the sample constitutes2 From where was the sample collectedOther
First name of sampler or witnessed byj Last name of sampler or witnessed bylight
Title of samplerUnknown Laboratory sample identification258393
The fabricator/manufacturer/facility namena Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifierUnknown
Structure nameUnknown
Material Information
Material TypeConcrete The concrete mix design number00000000000000
The truck number from where the sample was collectedUnknown The batch plant ticket number from where the sample was collected000000000000000
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedUnknown Where the material sample would have been placed if not sampledNot set
From Lot No.Not set Bag Lot No.Not set
Test Details
DIME Sample ID: 2014-10-21-1
DIME Test ID: 2014-10-21-1-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-11-18
Test Results

Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: SV
Date of test: 11/18/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 5.99 in
Average diameter of cylinder 2: 5.99 in
Maximum load on cylinder 1: 129635 lb
Maximum load on cylinder 2: 133505 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 28 days
Cross sectional area of cylinder 1: 28.18 in^2
Cross sectional area of cylinder 2: 28.18 in^2
Compressive strength of cylinder 1: 4600.2 psi
Compressive strength of cylinder 2: 4737.6 psi
Compressive strength (to nearest 10 psi):4670 psi
General comments (publicly viewable) (Max 1000 characters):
Test Graph
Source: Partner Data Point File
Test graph for Cylinder Code 1 of 2

Source: Partner Data Point File
Test graph for Cylinder Code 2 of 2

Test was verified on 11/18/2014