Summary for Test 2014-08-21-15-1

Test performed: ASTM C39-10

Project Information

Project IdentifiersProject ID: 1841
DEA: 041706U4
EFIS: 0400000450
DIST-CO-RTE-PM04-ALA-880-30.0/ 31.0
Award Date03/25/2009
Closeout Date01/14/2016
Work Description5th Avenue Overhead Bridge Replacement
Location Description5th Ave and 880. Â
QA Service Level1 (Verified on 02/09/2012)

Sample Information

Sample Taken Date08/21/2014 Sample Unique Key15
Will the laboratory/organization for which you are a member perform testing on this material sample?Yes Date that the sample was received by the laboratory/organization performing the testing08/21/2014
Sample typeQuality Control A brief description of the sampleconcrete cylinder
The quantity of what the sample constitutes2 concrete cylinder From where was the sample collectedOther
First name of sampler or witnessed byA Last name of sampler or witnessed byPannu
Title of samplerSR Telephone number of samplerUnknown
Laboratory sample identificationcl141118 Linked DIME Sample ID0
The fabricator/manufacturer/facility namefield Transportation Laboratory (TL) Number
Inspector Lot Number from the Transportation Laboratory (TL) Form Structure unique identifierUnknown
Structure nameUnknown

Material Information

Material TypeConcrete The concrete mix design numberd20pp5e1
The truck number from where the sample was collectedUnknown The batch plant ticket number from where the sample was collectedna
Concrete batch plantUnknown The fabricator/manufacturer designation for the sampleUnknown
A detailed description of where the material sample was collectedfield Where the material sample would have been placed if not sampledNot set
From Lot No.Not set Bag Lot No.Not set

Test Details

DIME Sample ID: 2014-08-21-15
DIME Test ID: 2014-08-21-15-1
Testing Lab: CT HQ - Sacramento Concrete Testing Laboratory
Test Method: ASTM C39-10: Standard Test Method for Compressive Strength of Cylindrical Concrete Specimens
Test Release Date: 2014-10-02

Test Results


Unit system used?: US Units
Number of specimens: 2
Test performed: With no density determined
Input Type: Measured
Tester's full name: Mike Mullins
Date of test: 10/02/2014
Capped in accordance with?: ASTM C617/CTM521
Average diameter of cylinder 1: 6.02 in
Average diameter of cylinder 2: 6.01 in
Maximum load on cylinder 1: 155362 lb
Maximum load on cylinder 2: 159314 lb
Type of fracture pattern of cylinder 1: 1
Type of fracture pattern of cylinder 2: 1
Comment on any defect in either specimen or caps (Max 250 Characters): no data
Correction factor for cylinder 1: 1
Correction factor for cylinder 2: no data
Age of specimen: 42 days
Cross sectional area of cylinder 1: 28.46 in^2
Cross sectional area of cylinder 2: 28.37 in^2
Compressive strength of cylinder 1: 5459.0 psi
Compressive strength of cylinder 2: 5615.6 psi
Compressive strength (to nearest 10 psi): 5540 psi
General comments (publicly viewable) (Max 1000 characters):

Test was verified on 10/2/2014